2-27. Duct static pressure setting
¢ Low static pressure duct (Mini duct) type, Low static pressure
duct (Slim duct)/Slim concealed floor type, Low static pressure
duct (High efficiency) type, Medium static pressure duct type,
and 72/90/96GTEH in High static pressure duct type
When the external static pressure is different from the normal static pressure, change the airflow set-
ting.
Setting of airflow can be changed by wireless remote controller, wired remote controller, and simple
remote controller.
How to set airflow (external static pressure):
• Wireless remote controller
Airflow is set by function number 26 (static pressure).
For details, refer to the following sections:
–
"Button name and function"
–
"Indoor unit (setting by wireless remote controller)"
–
"Function details"
• Wired remote controller (UTY-RNK)
Airflow is set by function number 26 (static pressure).
For details, refer to the following sections:
–
"Button name and function"
–
"Indoor unit (setting by UTY-RNK)"
–
"Function details"
• Wired remote controller (UTY-RLR)
Airflow is set by function number 26 (static pressure).
For details, refer to the following sections:
–
"Indoor unit (setting by UTY-RLR)"
–
"Function details"
• Simple remote controller (UTY-RSK, UTY-RHK)
Airflow is set by function number 26 (static pressure).
For details, refer to the following sections:
–
"Button name and function"
–
"Indoor unit (setting by UTY-RSK, UTY-RHK)"
–
"Function details"
• Simple remote controller (UTY-RSR, UTY-RHR)
Airflow is set by function number 26 (static pressure).
For details, refer to the following sections:
–
"Indoor unit (setting by UTY-RSR, UTY-RHR)"
–
"Function details"
• Wired remote controller (Touch panel)
Airflow is set by function number 26 (static pressure).
For details, refer to the following sections:
–
"Indoor unit (setting by UTY-RNRZ)"
–
"Function details"
2-27. Duct static pressure setting
on page 07-17
on page 07-108
on page 07-28
on page 07-93
on page 07-108
on page 07-105
on page 07-108
on page 07-40
on page 07-108
on page 07-108
on page 07-102
on page 07-108
- (07-144) -
on page 07-87
on page 07-99
on page 07-96
2. Function settings