3-2. Network converter (UTY-VTGXV)
¢ Accessory
Name and shape
Cable tie
Screw (M4 × 16 mm)
Installation manual
3-2. Network converter (UTY-VTGXV)
•
With this Network converter, single split type and multi system air condition-
ers can be controlled by System controller, Touch panel controller, Central
remote controller in VRF network system or by Wired remote controller con-
nected to the Network converter.
•
Start/Stop, operation mode, temperature setting, fan speed, etc. can be
done with these controllers.
•
One Network converter can be connected and controlled up to 16 indoor
units.
•
Two Wired remote controllers are possible for one Network converter by
UTY-VTGXV.
•
Up to 100 Network converters can be connected in one VRF network sys-
tem. (One Network converter is regarded as one refrigerant system. Total
refrigerant systems in one VRF network system must be within 100.)
Q'ty
7
4
1
For mounting the remote controller cable and
transmission cable
For mounting the Network converter
- (05-120) -
Application
3. Adaptor/Convertor units