Fujitsu AIRSTAGE ASEH09KGTG Design & Technical Manual
Fujitsu AIRSTAGE ASEH09KGTG Design & Technical Manual

Fujitsu AIRSTAGE ASEH09KGTG Design & Technical Manual

Hide thumbs Also See for AIRSTAGE ASEH09KGTG:

Advertisement

Quick Links

AIR CONDITIONER
Wall mounted type
DESIGN & TECHNICAL MANUAL
INDOOR
ASEH07KGTG
ASEH09KGTG
ASEH12KGTG
ASEH14KGTG
OUTDOOR
AOEH07KGCG
AOEH09KGCG
AOEH12KGCG
AOEH14KGCG
DR_AS229ES_01
2024.02.20

Advertisement

loading

Summary of Contents for Fujitsu AIRSTAGE ASEH09KGTG

  • Page 1 AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASEH07KGTG ASEH09KGTG ASEH12KGTG ASEH14KGTG OUTDOOR AOEH07KGCG AOEH09KGCG AOEH12KGCG AOEH14KGCG DR_AS229ES_01 2024.02.20...
  • Page 2 App Store is a service mark of Apple Inc., registered in the U.S. and other countries. IOS is a trademark or registered trademark of Cisco in the U.S. and other countries and is used under license. Copyright © 2024 Fujitsu General Limited. All rights reserved.
  • Page 3 CONTENTS Part 1. INDOOR UNIT................1 1. Specifications....................2 2. Wireless LAN control ..................4 2-1. System requirement......................4 3. Dimensions....................5 3-1. Models: ASEH07KGTG, ASEH09KGTG, ASEH12KGTG, and ASEH14KGTG ....5 3-2. Pipe exit length from the rear ...................7 4. Wiring diagrams ....................8 4-1. Models: ASEH07KGTG, ASEH09KGTG, ASEH12KGTG, and ASEH14KGTG ....8 5.
  • Page 4 CONTENTS (continued) Part 2. OUTDOOR UNIT..............49 1. Specifications....................50 2. Dimensions....................51 2-1. Models: AOEH07KGCG, AOEH09KGCG, AOEH12KGCG, and AOEH14KGCG..51 3. Installation space ..................52 3-1. Models: AOEH07KGCG, AOEH09KGCG, AOEH12KGCG, and AOEH14KGCG..52 4. Refrigerant circuit ..................55 4-1. Models: AOEH07KGCG, AOEH09KGCG, AOEH12KGCG, and AOEH14KGCG..55 5. Wiring diagrams ..................56 5-1.
  • Page 5 Part 1. INDOOR UNIT WALL MOUNTED TYPE: ASEH07KGTG ASEH09KGTG ASEH12KGTG ASEH14KGTG...
  • Page 6 1. Specifications Wall mounted Type Inverter, Heat pump Model name ASEH07KGTG ASEH09KGTG ASEH12KGTG ASEH14KGTG Power supply 230 V~ 50 Hz Power supply intake Outdoor unit Available voltage range 198—264 V Rated Btu/h 6,800 8,500 11,600 14,300 Cooling 0.9—3.3 0.9—3.6 0.9—4.1 0.9—4.5 Min.—Max.
  • Page 7 Wall mounted Type Inverter, Heat pump Model name ASEH07KGTG ASEH09KGTG ASEH12KGTG ASEH14KGTG NOTES: • Specifications are based on the following conditions: – Cooling: Indoor temperature of 27°CDB/19°CWB, and outdoor temperature of 35°CDB/24°CWB. – Heating: Indoor temperature of 20°CDB/15°CWB, and outdoor temperature of 7°CDB/6°CWB. –...
  • Page 8 After installation of mobile app, user registration is required. For user registration and setup infor- mation, refer to Setting Manual attached with the product. For the latest version of the wireless LAN control manuals, refer to the following web site. https://www.fujitsu-general.com/global/support/ - 4 - 2-1. System requirement...
  • Page 9 3. Dimensions 3-1. Models: ASEH07KGTG, ASEH09KGTG, ASEH12KGTG, and ASEH14KGTG Unit: mm 373.5 417.5 (834) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 5 - 3-1. Models: ASEH07KGTG, ASEH09KGTG, ASEH12KGTG, and ASEH14KGTG 3. Dimensions...
  • Page 10 ¢ Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 70 or more Wall hook bracket 107 or more 183 or more Outline of the indoor unit 1,500 or more A: Install so that the flare connection part is outdoors. - 6 - 3-1.
  • Page 11 3-2. Pipe exit length from the rear Design the system considering the length of the pipes or hose exiting from the rear of the indoor unit. NOTE: Detailed shapes of the indoor unit and the tip of each pipe or hose may vary depending on the model.
  • Page 12 4. Wiring diagrams 4-1. Models: ASEH07KGTG, ASEH09KGTG, ASEH12KGTG, and ASEH14KGTG - 8 - 4-1. Models: ASEH07KGTG, ASEH09KGTG, ASEH12KGTG, and ASEH14KGTG 4. Wiring diagrams...
  • Page 13 5. Capacity table Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 5-1.
  • Page 14 ¢ Model: ASEH14KGTG Indoor temperature °CDB °CWB °CDB 3.35 2.71 0.36 3.74 2.97 0.43 4.14 3.16 0.50 4.34 3.22 0.51 4.48 3.30 0.45 4.78 3.35 0.51 5.01 3.43 0.51 3.57 2.95 0.59 3.87 3.06 0.62 4.07 3.13 0.58 4.27 3.21 0.59 4.37 3.26...
  • Page 15 5-2. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: ASEH07KGTG Indoor temperature °CDB °CWB 3.12 1.22 3.13 1.30 3.13 1.30 3.13 1.34 3.07 1.35 3.08 1.10 3.08 1.15 3.08 1.15 3.08 1.19 3.04 1.20...
  • Page 16 6. Fan performance 6-1. Air velocity distributions ¢ Model: ASEH07KGTG Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center...
  • Page 17 ¢ Models: ASEH09KGTG and ASEH12KGTG Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view...
  • Page 18 ¢ Model: ASEH14KGTG Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view Horizontal louver: Down...
  • Page 19 6-2. Airflow ¢ Model: ASEH07KGTG  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 15 - 6-2. Airflow 6. Fan performance...
  • Page 20 ¢ Model: ASEH09KGTG  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 16 - 6-2. Airflow 6. Fan performance...
  • Page 21 ¢ Model: ASEH12KGTG  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 17 - 6-2. Airflow 6. Fan performance...
  • Page 22 ¢ Model: ASEH14KGTG  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 18 - 6-2. Airflow 6. Fan performance...
  • Page 23 7. Operation noise (sound pressure) 7-1. Noise level curve ¢ Model: ASEH07KGTG  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 HIGH HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET 1,000...
  • Page 24 ¢ Model: ASEH12KGTG  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 25 7-2. Sound level check point Microphone Microphone NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated above. - 21 - 7-2. Sound level check point 7. Operation noise (sound pressure)
  • Page 26 8. Safety devices Model Type of protection Protection form ASEH07KGTG ASEH09KGTG Circuit protection Current fuse (PCB*) 250 V, 3.15 A 110 ±15°C Activate Fan motor speed down Fan motor protection Thermistor protection 110 ±15°C Reset Fan motor speed recover Model Type of protection Protection form ASEH12KGTG...
  • Page 27 9. External input and output External Input and Output PCB Indoor unit PCB CN47 (Ext. out) CN65 (Ext. in/out PCB) CN46 (Ext. in) SW301 SW302 Rotary switch CN314 CN313 CN312 CN311 CN310 CN308 Connecting point Input/Output Function Input select Input signal Operation/Stop CN46 Input...
  • Page 28 9-1. External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
  • Page 29 ¢ External Input and Output PCB The indoor unit Operation/Stop can be set by using the input connector on the PCB. • Input select Use either one of these types of connectors according to the application. (Both types of connec- tors cannot be used simultaneously.) –...
  • Page 30 ¢ Input signal type • Indoor unit Input signal type is only "Edge". Edge • External Input and Output PCB The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch 2 (SW302) on the External Input and Output PCB.
  • Page 31 9-2. External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. ¢ Indoor unit • A twisted pair cable should be used. Maximum length of cable is 25 m. •...
  • Page 32 ¢ External Input and Output PCB • A twisted pair cable should be used. Maximum length of cable is 25 m. • Output voltage: High DC 12 V ±2 V, Low 0 V. • Permissible current: 50 mA • For details, refer to "Setting of external input and output"...
  • Page 33 9-3. Setting of external input and output • Indoor unit Input Connection point Function setting number 46 Function Operation/Stop mode 1 (R.C. enabled) (Setting prohibited) CN46 Forced stop mode Operation/Stop mode 2 (R.C. disabled) Output Connection point Function setting number 60 Function Operation/Stop 01 to 08...
  • Page 34 9-4. Details of control input function ¢ Operation/Stop mode 1 • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary SW302 switch Off → On Operation — Input of indoor unit CN46 On →...
  • Page 35 ¢ Forced stop • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary SW302 switch Forced stop Off → On (R.C. disabled) — Input of indoor unit CN46 Normal On → Off (R.C.
  • Page 36 ¢ Operation/Stop mode 2 • In the case of “Edge” input External Input and Output PCB Function External input Input signal Command setting Rotary SW302 switch Operation Off → On (R.C. enabled) — Input of indoor unit CN46 Stop On → Off (R.C.
  • Page 37 ¢ Forced thermostat off External Input and Output External input Input signal Command Rotary switch Off → On Thermostat off External Input and 2, B, C, D CN313 Output PCB On → Off Normal operation CN313 Compressor Room temp. Set temp. - 33 - 9-4.
  • Page 38 9-5. Details of control output function ¢ Operation status External Input and Function Output PCB External output Output signal Status setting Rotary switch Off → On Operation 60-00 1, 2 Output of indoor unit CN47 On → Off Stop Off → On Operation External Input and —...
  • Page 39 ¢ Indoor unit fan operation status External Input and Function Output PCB External output Output signal Status setting Rotary switch Off → On Fan run 60-10 Output of indoor unit CN47 On → Off Fan stop Off → On Fan run External Input and —...
  • Page 40 10. Group connection NOTE: Group control cannot be used together with WLAN Adapter. Installation procedure for group control system: A number of indoor units can be operated at the same time using a single remote controller. NOTE: When different type of indoor units (such as wall-mounted type and cassette type, cassette type and duct type, or other combinations) are connected using group control system, some functions may no longer be available.
  • Page 41 11. Remote controller 11-1. Wireless remote controller ¢ Overview Signal SENSOR button transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button...
  • Page 42 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 43 12. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 12-1. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting proce- dure and the content of each function setting, select appropriate functions for your installation envi- ronment.
  • Page 44 NOTES: • The air conditioner custom code is set to prior to shipment. • If you do not know the air conditioner custom code setting, try each of the custom codes ( → → → ) until you find the code that operates the air conditioner. ¢...
  • Page 45 2) Room temperature control for indoor unit sensor Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature of the room temperature sensor is corrected as follows: Corrected temp.
  • Page 46 3) Room temperature control for wired remote controller sensor Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
  • Page 47 6) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 7) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description...
  • Page 48 10) Switching functions for external output terminal Functions of the external output terminal can be switched. For details, refer to “External input and output”. Function number Setting value Setting description Factory setting Operation status ♦ 01—08 (Setting prohibited) Error status Indoor unit fan operation status (Setting prohibited) - 44 -...
  • Page 49 12-2. Custom code setting for wireless remote controller To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code.
  • Page 50 13. Accessories 13-1. Models: ASEH07KGTG, ASEH09KGTG, ASEH12KGTG, and ASEH14KGTG Part name Exterior Part name Exterior Operation manual Cloth tape Self-tapping screw Installation manual (large) Self-tapping screw Remote controller (small) Battery Wall hook bracket Remote controller Filter holder holder Installation spacer Air cleaning filters Operation manual (CD-ROM)
  • Page 51 14. Optional parts 14-1. Controllers Exterior Part name Model name Summary Remote controller that provides the functions you need in a sleek design that uniquely transforms itself to blend Wired Remote with any interior. Controller UTY-RVRY Wire type: Non-polar 2-wire (Touch Panel) Optional Communication Kit is necessary for installation.
  • Page 52 14-2. Others Exterior Part name Model name Summary Air Cleaning Air Cleaning Filter can be mounted to UTR-FA16-5 Filter the indoor unit. Use to connect with various peripheral devices and air conditioner PCB. External UTY-XWZX Connect Kit Connecting point: CN46 and CN47 on Main PCB Required when external device is connected.
  • Page 53 Part 2. OUTDOOR UNIT SINGLE TYPE: AOEH07KGCG AOEH09KGCG AOEH12KGCG AOEH14KGCG...
  • Page 54 1. Specifications Type Inverter, Heat pump Model name AOEH07KGCG AOEH09KGCG AOEH12KGCG AOEH14KGCG Power supply 230 V~ 50 Hz Power supply intake Outdoor unit Available voltage range 198—264 V Starting current Cooling 1,390 1,480 1,800 Airflow rate Heating 1,350 1,420 1,690 Type ×...
  • Page 55 2. Dimensions 2-1. Models: AOEH07KGCG, AOEH09KGCG, AOEH12KGCG, and AOEH14KGCG Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 51 - 2-1. Models: AOEH07KGCG, AOEH09KGCG, AOEH12KGCG, and AOEH14KGCG 2.
  • Page 56 3. Installation space 3-1. Models: AOEH07KGCG, AOEH09KGCG, AOEH12KGCG, and AOEH14KGCG ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
  • Page 57  Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
  • Page 58  Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
  • Page 59 4. Refrigerant circuit 4-1. Models: AOEH07KGCG, AOEH09KGCG, AOEH12KGCG, and AOEH14KGCG Heat exchanger 3-way 2-way (INDOOR) valve valve Muffler Muffler 4-way valve Strainer Expansion valve Heat exchanger Strainer (OUTDOOR) Cooling Heating : Thermistor (Discharge temperature) : Thermistor (Outdoor temperature) : Thermistor (Heat exchanger out temperature) : Thermistor (Pipe temperature) : Thermistor (Room temperature) - 55 -...
  • Page 60 5. Wiring diagrams 5-1. Models: AOEH07KGCG, AOEH09KGCG, AOEH12KGCG, and AOEH14KGCG - 56 - 5-1. Models: AOEH07KGCG, AOEH09KGCG, AOEH12KGCG, and AOEH14KGCG 5. Wiring diagrams...
  • Page 61 6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Models: AOEH07KGCG, AOEH09KGCG, AOEH12KGCG, and AOEH14KGCG NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 62 7. Additional charge calculation 7-1. Models: AOEH07KGCG and AOEH09KGCG Refrigerant type Factory charge amount ¢ Refrigerant charge Total pipe length 15 or less 20 (Max.) 20 g/m Additional charge amount 7-2. Models: AOEH12KGCG and AOEH14KGCG Refrigerant type Factory charge amount ¢...
  • Page 63 8. Airflow 8-1. Model: AOEH07KGCG  Cooling 1,390  Heating 1,350 8-2. Model: AOEH09KGCG  Cooling 1,480  Heating 1,420 8-3. Models: AOEH12KGCG and AOEH14KGCG  Cooling 1,800 1,059  Heating 1,690 - 59 - 8-1. Model: AOEH07KGCG 8. Airflow...
  • Page 64 9. Operation noise (sound pressure) 9-1. Noise level curve ¢ AOEH07KGCG  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 65 ¢ AOEH12KGCG  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz ¢...
  • Page 66 9-2. Sound level check point Rear Microphone Microphone Airflow Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above. - 62 - 9-2. Sound level check point 9. Operation noise (sound pressure)
  • Page 67 10. Electrical characteristics Model name AOEH07KGCG AOEH09KGCG AOEH12KGCG AOEH14KGCG Voltage 230 ~ Power supply Frequency 10.5 Max operating current* Starting current Circuit breaker current Power cable Wiring spec.* Connection cable* Limited wiring length NOTES: • * : Maximum operating current is the total current of the indoor unit and the outdoor unit. •...
  • Page 68 11. Safety devices Model Type of protection Protection form AOEH07KGCG AOEH09KGCG 250 V, 20 A Circuit protection Current fuse (Main PCB) 250 V, 5 A 103 ±18°C Activate Fan motor stop Fan motor Terminal protection protection program 95 ±18°C Reset Fan motor restart 110°C Activate...
  • Page 69 12. Accessories 12-1. Models: AOEH07KGCG, AOEH09KGCG, AOEH12KGCG, and AOEH14KGCG Part name Exterior Part name Exterior Installation manual Drain pipe - 65 - 12-1. Models: AOEH07KGCG, AOEH09KGCG, AOEH12KGCG, and AOEH14KGCG 12. Accessories...