hit counter code
Fujitsu ARXG07KSLAP Design & Technical Manual
Fujitsu ARXG07KSLAP Design & Technical Manual

Fujitsu ARXG07KSLAP Design & Technical Manual

2-unit multi-split type
Hide thumbs Also See for ARXG07KSLAP:
Table of Contents

Advertisement

Quick Links

AIR CONDITIONER
2-unit multi-split type
DESIGN & TECHNICAL MANUAL
INDOOR
ASYG07–14KGTE
ASYG07–14KGTF
OUTDOOR
AUXG07–14KVLA
ARXG07–14KSLAP ARXG07–14KLLAP
ASYG07–14KMTB
ASYG07–14KETA
ASYG07–14KMCC
ASYG07–14KMCE
ASYG07–14KMCF
AOYG14KBTA2
ASYG07–14KETA-B
ASYG07–14KETE
ASYG07–14KETE-B
ASYG07–14KETF
ASYG07–14KETF-B
AOYG18KBTA2
ASYG07–14KGTB
AGYG09–14KVCA
DR_MU021EF_09
2023.03.10

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu ARXG07KSLAP

  • Page 1 AIR CONDITIONER 2-unit multi-split type DESIGN & TECHNICAL MANUAL INDOOR AUXG07–14KVLA ARXG07–14KSLAP ARXG07–14KLLAP ASYG07–14KGTB ASYG07–14KGTE ASYG07–14KMTB ASYG07–14KETA ASYG07–14KETA-B AGYG09–14KVCA ASYG07–14KGTF ASYG07–14KMCC ASYG07–14KETE ASYG07–14KETE-B ASYG07–14KMCE ASYG07–14KETF ASYG07–14KETF-B ASYG07–14KMCF OUTDOOR AOYG14KBTA2 AOYG18KBTA2 DR_MU021EF_09 2023.03.10...
  • Page 2 • For further details, please check with our authorized dealer. Trademarks ™ FGLair is trademark of FUJITSU GENERAL LIMITED in the United States, other countries or both. “AIRSTAGE Mobile” is a trademark of FUJITSU GENERAL LIMITED. Android and Google Play are trademarks of Google LLC.
  • Page 3: Table Of Contents

    CONTENTS Part 1. INDOOR UNIT................1 1. Model lineup ....................2 1-1. Connectable indoor units to each outdoor unit..............4 1-2. Indoor unit connection patterns..................5 2. Specifications....................6 2-1. Compact cassette type ....................6 2-2. Mini duct type........................7 2-3. Slim duct type ........................8 2-4. Wall mounted type ......................9 2-5.
  • Page 4 CONTENTS (continued) 9-2. Mini duct type.......................107 9-3. Slim duct type ......................109 9-4. Wall mounted type .......................111 9-5. Floor type........................115 9-6. Sound level check point ....................117 10. Electrical characteristics ................120 11. Safety devices ...................122 12. External input and output.................124 12-1.Compact cassette, Mini duct, and Slim duct types ............124 12-2.Wall mounted type (KGTB, KETA, and KETA-B) ............130 12-3.Wall mounted type (KMTB and KMCC) ..............140 12-4.Wall mounted type (KGTE, KGTF, KMCE, KMCF, KETE, KETE-B, KETF, and KETF-B)
  • Page 5 CONTENTS (continued) 16-3.Slim duct type ......................267 16-4.Wall mounted type ......................268 16-5.Floor type ........................272 17. Optional parts ...................273 17-1.Controllers ........................273 17-2.Cassette grille ......................277 17-3.Others .........................278 18. Indoor unit installation precautions ............284 18-1.Places where prohibited for use..................284 18-2.Points to remember when installing ................284...
  • Page 6 CONTENTS (continued) Part 2. OUTDOOR UNIT (2 UNITS TYPE) ........287 1. Specifications....................288 2. Dimensions....................290 2-1. Model: AOYG14KBTA2 ....................290 2-2. Model: AOYG18KBTA2 ....................291 3. Installation space ..................292 3-1. Models: AOYG14KBTA2 and AOYG18KBTA2 ............292 4. Refrigerant circuit ..................295 4-1. Model: AOYG14KBTA2 ....................295 4-2.
  • Page 7: Part 1. Indoor Unit

    Part 1. INDOOR UNIT COMPACT CASSETTE TYPE: AUXG07–14KVLA MINI DUCT TYPE: SLIM DUCT TYPE: ARXG07–14KSLAP ARXG07–14KLLAP WALL MOUNTED TYPE: ASYG07–14KGTB ASYG07–14KMTB ASYG07–14KGTE ASYG07–14KMCC ASYG07–14KGTF ASYG07–14KMCE ASYG07–14KMCF ASYG07–14KETA ASYG07–14KETA-B ASYG07–14KETE ASYG07–14KETE-B ASYG07–14KETF ASYG07–14KETF-B FLOOR TYPE: AGYG09–14KVCA...
  • Page 8: Model Lineup

    1. Model lineup Indoor unit AUXG07KVLA ARXG07KSLAP ARXG07KLLAP AUXG09KVLA ARXG09KSLAP ARXG09KLLAP AUXG12KVLA ARXG12KSLAP ARXG12KLLAP AUXG14KVLA ARXG14KSLAP ARXG14KLLAP ASYG07KGTB ASYG07KGTE ASYG07KMTB ASYG09KGTB ASYG09KGTE ASYG09KMTB ASYG12KGTB ASYG12KGTE ASYG12KMTB ASYG14KGTB ASYG14KGTE ASYG14KMTB ASYG07KGTF ASYG07KMCC ASYG09KGTF ASYG09KMCC ASYG12KGTF ASYG12KMCC ASYG14KGTF ASYG14KMCC ASYG07KMCE ASYG09KMCE ASYG12KMCE...
  • Page 9 Outdoor unit AOYG14KBTA2 AOYG18KBTA2 - 3 - 1. Model lineup...
  • Page 10: Connectable Indoor Units To Each Outdoor Unit

    1-1. Connectable indoor units to each outdoor unit ●: Connectable / -: Not connectable Compact cassette Mini duct Outdoor unit AUXG07–14KVLA ARXG07–14KSLAP Btu class kW class AOYG14KBTA2 ● ● ● — ● ● ● — AOYG18KBTA2 ● ● ● ● ●...
  • Page 11: Indoor Unit Connection Patterns

    1-2. Indoor unit connection patterns ¢ 2 units AOYG14KBTA2 Combination no. Unit 1 Unit 2 Total AOYG18KBTA2 Combination no. Unit 1 Unit 2 Total Numbers in column Unit 1, 2, and Total indicate the indoor unit capacities as follows: 7: 7,000 Btu/h, 9: 9,000 Btu/h, 12: 12,000 Btu/h, 14: 14,000 Btu/h ..- 5 - 1-2.
  • Page 12: Specifications

    2. Specifications 2-1. Compact cassette type Model name AUXG07KVLA AUXG09KVLA AUXG12KVLA AUXG14KVLA Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.15 0.19 0.22 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 13: Mini Duct Type

    2-2. Mini duct type Model name ARXG07KSLAP ARXG09KSLAP ARXG12KSLAP ARXG14KSLAP Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class HIGH Input power QUIET Running current 0.29 0.33 0.38 0.58 HIGH Cooling QUIET Airflow rate...
  • Page 14: Slim Duct Type

    2-3. Slim duct type Model name ARXG07KLLAP ARXG09KLLAP ARXG12KLLAP ARXG14KLLAP Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.33 0.30 0.35 0.51 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 15: Wall Mounted Type

    2-4. Wall mounted type Model name ASYG07KGTB ASYG09KGTB ASYG12KGTB ASYG14KGTB Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.29 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 16 Model name ASYG07KGTE ASYG09KGTE ASYG12KGTE ASYG14KGTE Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.29 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan ×...
  • Page 17 Model name ASYG07KGTF ASYG09KGTF ASYG12KGTF ASYG14KGTF Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.29 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan ×...
  • Page 18 Model name ASYG07KMTB ASYG09KMTB ASYG12KMTB ASYG14KMTB Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan ×...
  • Page 19 Model name ASYG07KMCC ASYG09KMCC ASYG12KMCC ASYG14KMCC Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan ×...
  • Page 20 Model name ASYG07KMCE ASYG09KMCE ASYG12KMCE ASYG14KMCE Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan ×...
  • Page 21 Model name ASYG07KMCF ASYG09KMCF ASYG12KMCF ASYG14KMCF Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan ×...
  • Page 22 ASYG07KETA ASYG09KETA ASYG12KETA ASYG14KETA Model name ASYG07KETA-B ASYG09KETA-B ASYG12KETA-B ASYG14KETA-B Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 23 ASYG07KETE ASYG09KETE ASYG12KETE ASYG14KETE Model name ASYG07KETE-B ASYG09KETE-B ASYG12KETE-B ASYG14KETE-B Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 24 ASYG07KETF ASYG09KETF ASYG12KETF ASYG14KETF Model name ASYG07KETF-B ASYG09KETF-B ASYG12KETF-B ASYG14KETF-B Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 25: Floor Type

    2-5. Floor type Model name AGYG09KVCA AGYG12KVCA AGYG14KVCA Power supply 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.15 0.18 0.20 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan ×...
  • Page 26: Wireless Lan Control (For Kgtf, Kmcf, Ketf, And Ketf-B)

    After installation of mobile app, user registration is required. For user registration and setup infor- mation, refer to Setting Manual attached with the product. For the latest version of the wireless LAN control manuals, refer to the following web site. https://www.fujitsu-general.com/global/support/ - 20 - 3-1. System requirement...
  • Page 27: Wireless Lan Function List

    3-2. Wireless LAN function list NOTE: To use the wireless LAN control, user registration in advance and access to the wireless home network are required. Attached Wireless Item Mobile app Remote Controller Air conditioning Operation on/off ○ ○ control function Operation mode setting ○...
  • Page 28: Dimensions

    4. Dimensions 4-1. Compact cassette type ¢ Models: AUXG07–14KVLA Unit: mm Grid type grille Hanging bolt position IR receiver Drain hose View A Ceiling Control Box View B View C - 22 - 4-1. Compact cassette type 4. Dimensions...
  • Page 29  Installation space requirement Unit: mm Strong and durable ceiling or more 1,000 1,000 or more or more 1,800 or more Obstruction Floor Maximum height from floor to ceiling (Unit: mm) 07 and 09 models 12 or larger models Standard 2,700 High ceiling —...
  • Page 30: Mini Duct Type

    4-2. Mini duct type ¢ Models: ARXG07–14KSLAP Unit: mm Rear view View A Drain port P 100 × 6 = 600 Top view Side view Front view Bottom view - 24 - 4-2. Mini duct type 4. Dimensions...
  • Page 31  Installation space requirement Provide sufficient installation space for product safety. Unit: mm Strong and durable ceiling Indoor unit Left Right side side or more* or more *: 400 or more when drain from drain pipe • When intaking air from back: •...
  • Page 32: Slim Duct Type

    4-3. Slim duct type ¢ Models: ARXG07–14KLLAP Unit: mm View A Rear view (Drain hose) Drain port 100 x 6 = 600 Side view Top view Front view Bottom view - 26 - 4-3. Slim duct type 4. Dimensions...
  • Page 33  Installation space requirement Provide sufficient installation space for product safety. In ceiling-concealed installations: Unit: mm 300 or more Strong and durable ceiling 20 or more Indoor unit Left Right side side 20 or more Service access Ceiling or more or more Floor ...
  • Page 34: Wall Mounted Type

    4-4. Wall mounted type ¢ Models: ASYG07–14KGTB Unit: mm 373.5 417.5 Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 28 - 4-4. Wall mounted type 4. Dimensions...
  • Page 35  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 70 or more 40 or more Wall hook bracket Outline of the indoor unit 107 or more 183 or more 1,500 or more A: Install so that the flare connection part is outdoors. - 29 - 4-4.
  • Page 36 ¢ Models: ASYG07–14KGTE and ASYG07–14KGTF Unit: mm 373.5 417.5 (834) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 30 - 4-4. Wall mounted type 4. Dimensions...
  • Page 37  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 70 or more Wall hook bracket 107 or more 183 or more Outline of the indoor unit 1,500 or more A: Install so that the flare connection part is outdoors. - 31 - 4-4.
  • Page 38 ¢ Models: ASYG07–14KMTB and ASYG07–14KMCC Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 32 - 4-4. Wall mounted type 4. Dimensions...
  • Page 39  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 70 or more 40 or more Wall hook bracket Outline of the indoor unit 107 or more 183 or more 1,500 or more A: Install so that the flare connection part is outdoors. - 33 - 4-4.
  • Page 40 ¢ Models: ASYG07–14KMCE and ASYG07–14KMCF Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 34 - 4-4. Wall mounted type 4. Dimensions...
  • Page 41  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 70 or more Wall hook bracket 107 or more 183 or more Outline of the indoor unit 1,500 or more A: Install so that the flare connection part is outdoors. - 35 - 4-4.
  • Page 42 ¢ Models: ASYG07–14KETA, ASYG07–14KETA-B, ASYG07– 14KETE, ASYG07–14KETE-B, ASYG07–14KETF, and ASYG07– 14KETF-B Unit: mm 373.5 417.5 (950) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 36 - 4-4. Wall mounted type 4. Dimensions...
  • Page 43  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 40 or more Wall hook bracket Outline of the indoor unit 166 or more 211 or more 1,500 or more The flare connection part should be installed outdoors.
  • Page 44: Floor Type

    4-5. Floor type ¢ Models: AGYG09–14KVCA Unit: mm Side view Front view - 38 - 4-5. Floor type 4. Dimensions...
  • Page 45  Installation space Unit: mm 100 or more 80 or more 80 or more 50 or more 150 or below from the floor PROHIBITED Grating WARNING • The appliance shall be installed, operated and stored in a room with a floor area larger than X Minimum room area Amount of refrigerant charge M (kg)
  • Page 46: Wiring Diagrams

    5. Wiring diagrams 5-1. Compact cassette type ¢ Models: AUXG07–14KVLA - 40 - 5-1. Compact cassette type 5. Wiring diagrams...
  • Page 47: Mini Duct Type And Slim Duct Type

    5-2. Mini duct type and Slim duct type ¢ Models: ARXG07–14KSLAP and ARXG07–14KLLAP WLAN adapter, Converter etc. (Option) - 41 - 5-2. Mini duct type and Slim duct type 5. Wiring diagrams...
  • Page 48: Wall Mounted Type

    5-3. Wall mounted type ¢ Models: ASYG07–14KGTB - 42 - 5-3. Wall mounted type 5. Wiring diagrams...
  • Page 49 ¢ Models: ASYG07–14KGTE - 43 - 5-3. Wall mounted type 5. Wiring diagrams...
  • Page 50 ¢ Models: ASYG07–14KGTF - 44 - 5-3. Wall mounted type 5. Wiring diagrams...
  • Page 51 ¢ Models: ASYG07–14KMTB - 45 - 5-3. Wall mounted type 5. Wiring diagrams...
  • Page 52 ¢ Models: ASYG07–14KMCC - 46 - 5-3. Wall mounted type 5. Wiring diagrams...
  • Page 53 ¢ Models: ASYG07–14KMCE - 47 - 5-3. Wall mounted type 5. Wiring diagrams...
  • Page 54 ¢ Models: ASYG07–14KMCF - 48 - 5-3. Wall mounted type 5. Wiring diagrams...
  • Page 55 ¢ Models: ASYG07–14KETA and ASYG07–14KETA-B - 49 - 5-3. Wall mounted type 5. Wiring diagrams...
  • Page 56 ¢ Models: ASYG07–14KETE and ASYG07–14KETE-B - 50 - 5-3. Wall mounted type 5. Wiring diagrams...
  • Page 57 ¢ Models: ASYG07–14KETF and ASYG07–14KETF-B - 51 - 5-3. Wall mounted type 5. Wiring diagrams...
  • Page 58: Floor Type

    5-4. Floor type ¢ Models: AGYG09–14KVCA - 52 - 5-4. Floor type 5. Wiring diagrams...
  • Page 59: Air Velocity And Temperature Distributions

    6. Air velocity and temperature distributions 6-1. Compact cassette type ¢ Models: AUXG07–09KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 0.25 Top view Horizontal louver: Up 0.25 0.25 4 (m) Unit : m/s Side view Horizontal louver: Up 0.25...
  • Page 60 • Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Horizontal louver: Down 0.25 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data...
  • Page 61 ¢ Model: AUXG12KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 0.25 Top view Horizontal louver: Up 0.25 0.25 4 (m) Unit : m/s Side view Horizontal louver: Up 0.25 0.25 4 (m) - 55 - 6-1.
  • Page 62 • Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Horizontal louver: Down 0.25 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data...
  • Page 63 ¢ Model: AUXG14KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 Top view Horizontal louver: Up 0.25 0.25 0.25 4 (m) Unit : m/s Side view Horizontal louver: Up 0.25 0.25 4 (m) - 57 - 6-1.
  • Page 64 • Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Horizontal louver: Down 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data HIGH...
  • Page 65: Mini Duct Type

    6-2. Mini duct type ¢ Model: ARXG07KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center...
  • Page 66 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 60 - 6-2.
  • Page 67 ¢ Model: ARXG09KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 68 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 62 - 6-2.
  • Page 69 ¢ Model: ARXG12KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 70 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 64 - 6-2.
  • Page 71 ¢ Model: ARXG14KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 72 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 66 - 6-2.
  • Page 73: Slim Duct Type

    6-3. Slim duct type ¢ Model: ARXG07KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up...
  • Page 74 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 68 - 6-3.
  • Page 75 ¢ Model: ARXG09KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 76 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 70 - 6-3.
  • Page 77 ¢ Model: ARXG12KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 78 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 72 - 6-3.
  • Page 79 ¢ Model: ARXG14KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 80 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 74 - 6-3.
  • Page 81: Wall Mounted Type

    6-4. Wall mounted type ¢ Models: ASYG07–09KGTB, ASYG07–09KGTE, ASYG07– 09KGTF, ASYG07–12KMTB, ASYG07–12KMCC, ASYG07– 12KMCE, ASYG07–12KMCF, ASYG07–12KETA, ASYG07– 12KETA-B, ASYG07–12KETE, ASYG07–12KETE-B, ASYG07– 12KETF, and ASYG07–12KETF-B Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up...
  • Page 82 ¢ Models: ASYG12–14KGTB, ASYG12–14KGTE, ASYG12– 14KGTF, ASYG14KMTB, ASYG14KMCC, ASYG14KMCE, ASYG14KMCF, ASYG14KETA, ASYG14KETA-B, ASYG14KETE, ASYG14KETE-B, ASYG14KETF, and ASYG14KETF-B Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 83: Floor Type

    6-5. Floor type ¢ Models: AGYG09–14KVCA Fan speed Operation mode Fan select Measuring conditions HIGH Upper and lower Unit: m/s Top view Horizontal louver: Up Vertical louver: Center UPPER LOWER Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up...
  • Page 84: Fan Performance

    7. Fan performance NOTE: Airflow and capacity/outlet temperature curve data are measured based on the same condi- tions mentioned in "Specifications". 7-1. Mini duct type ¢ Model: ARXG07KSLAP Quiet (SP mode 00) SP mode 03 upper limit Quiet (Normal SP)
  • Page 85  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 79 - 7-1. Mini duct type 7. Fan performance...
  • Page 86 ¢ Model: ARXG09KSLAP Quiet (SP mode 00) SP mode 03 upper limit Quiet (Normal SP) Hi (SP mode 03) Quiet (SP mode 03) SP mode 00 upper limit SP mode 03 lower limit Normal SP upper limit Hi (Normal SP) Hi (SP mode 00) Airflow (m Available airflow rate range (High level)
  • Page 87  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 81 - 7-1. Mini duct type 7. Fan performance...
  • Page 88 ¢ Model: ARXG12KSLAP SP mode 03 upper limit Quiet (SP mode 03) Hi (SP mode 03) Quiet Normal SP (Normal SP) upper limit Quiet SP mode 03 (SP mode 00) lower limit SP mode 00 (Normal SP) upper limit Hi (SP mode 00) Airflow (m Available airflow rate range (High level) Hi (SP mode 03)
  • Page 89  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 83 - 7-1. Mini duct type 7. Fan performance...
  • Page 90 ¢ Model: ARXG14KSLAP Hi (SP mode 05) SP mode 05 upper limit Quiet (SP mode 00) Nomal SP Quiet upper limit (Nomal SP) Quiet Hi (Normal SP) (SP mode 05) SP mode 05 lower limit SP mode 00 upper limit (SP mode 00) Airflow (m Available airflow rate range (High level)
  • Page 91  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 85 - 7-1. Mini duct type 7. Fan performance...
  • Page 92: Slim Duct Type

    7-2. Slim duct type ¢ Model: ARXG07KLLAP Hi (SP mode 09) SP mode 09 upper limit Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) Hi (Normal SP) SP mode 00 Normal SP upper limit lower limited Quiet (SP mode 00)
  • Page 93  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 87 - 7-2. Slim duct type 7. Fan performance...
  • Page 94 ¢ Model: ARXG09KLLAP Hi (SP mode 09) SP mode 09 upper limit Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) Hi (Normal SP) Hi (SP mode00) SP mode 00 upper limit Quiet (SP mode 00) Airflow (m Available airflow rate range (High level) Hi (SP mode 09)
  • Page 95  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 89 - 7-2. Slim duct type 7. Fan performance...
  • Page 96 ¢ Model: ARXG12KLLAP SP mode 09 upper limit Hi (SP mode 09) Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) Hi (Normal SP) SP mode 00 Hi (SP mode 00) upper limit Quiet (SP mode 00) Airflow (m Available airflow rate range (High level)
  • Page 97  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 91 - 7-2. Slim duct type 7. Fan performance...
  • Page 98 ¢ Model: ARXG14KLLAP SP mode 09 upper limit Hi (SP mode 09) Quiet (SP mode 09) Nomal SP upper limit SP mode 09 lower limit Quiet (Nomal SP) Hi (Normal SP) SP mode 00 upper limit Hi (SP mode 00) Quiet (SP mode 00) 1,000...
  • Page 99  Characteristics of air volume and capacity • Cooling Capacity 1,000 Airflow (m • Heating Capacity 1,000 Airflow (m - 93 - 7-2. Slim duct type 7. Fan performance...
  • Page 100: Airflow

    8. Airflow Conversion factor: • 1 m /h = 0.2778 l/s = 0.5886 CFM • 3.6 m /h = 1 l/s • 1.699 m /h = 1 CFM 8-1. Compact cassette type Airflow Model Operation mode Fan speed High Cooling AUXG07KVLA Quiet AUXG09KVLA...
  • Page 101: Mini Duct Type

    8-2. Mini duct type Airflow Model Operation mode Fan speed High Cooling Quiet ARXG07KSLAP High Heating Quiet High Cooling Quiet ARXG09KSLAP High Heating Quiet High Cooling Quiet ARXG12KSLAP High Heating Quiet High Cooling Quiet ARXG14KSLAP High Heating Quiet - 95 - 8-2.
  • Page 102: Slim Duct Type

    8-3. Slim duct type Airflow Model Operation mode Fan speed High Cooling Quiet ARXG07KLLAP High Heating Quiet High Cooling Quiet ARXG09KLLAP High Heating Quiet High Cooling Quiet ARXG12KLLAP High Heating Quiet High Cooling Quiet ARXG14KLLAP High Heating Quiet - 96 - 8-3.
  • Page 103: Wall Mounted Type

    8-4. Wall mounted type Airflow Model Operation mode Fan speed High Cooling Quiet ASYG07KGTB High Heating Quiet High Cooling Quiet ASYG09KGTB High Heating Quiet High Cooling Quiet ASYG12KGTB High Heating Quiet High Cooling Quiet ASYG14KGTB High Heating Quiet High Cooling Quiet ASYG07KGTE High...
  • Page 104 Airflow Model Operation mode Fan speed High Cooling Quiet ASYG12KGTE High Heating Quiet High Cooling Quiet ASYG14KGTE High Heating Quiet High Cooling Quiet ASYG07KGTF High Heating Quiet High Cooling Quiet ASYG09KGTF High Heating Quiet High Cooling Quiet ASYG12KGTF High Heating Quiet High Cooling...
  • Page 105 Airflow Model Operation mode Fan speed High Cooling Quiet ASYG07KMTB High Heating Quiet High Cooling Quiet ASYG09KMTB High Heating Quiet High Cooling Quiet ASYG12KMTB High Heating Quiet High Cooling Quiet ASYG14KMTB High Heating Quiet High Cooling Quiet ASYG07KMCC High Heating Quiet High Cooling...
  • Page 106 Airflow Model Operation mode Fan speed High Cooling Quiet ASYG12KMCC High Heating Quiet High Cooling Quiet ASYG14KMCC High Heating Quiet High Cooling Quiet ASYG07KMCE High Heating Quiet High Cooling Quiet ASYG09KMCE High Heating Quiet High Cooling Quiet ASYG12KMCE High Heating Quiet High Cooling...
  • Page 107 Airflow Model Operation mode Fan speed High Cooling Quiet ASYG07KMCF High Heating Quiet High Cooling Quiet ASYG09KMCF High Heating Quiet High Cooling Quiet ASYG12KMCF High Heating Quiet High Cooling Quiet ASYG14KMCF High Heating Quiet High Cooling ASYG07KETA Quiet High ASYG07KETA-B Heating Quiet High...
  • Page 108 Airflow Model Operation mode Fan speed High Cooling ASYG12KETA Quiet ASYG12KETA-B High Heating Quiet High Cooling ASYG14KETA Quiet High ASYG14KETA-B Heating Quiet High Cooling ASYG07KETE Quiet ASYG07KETE-B High Heating Quiet High Cooling ASYG09KETE Quiet High ASYG09KETE-B Heating Quiet High Cooling ASYG12KETE Quiet High...
  • Page 109 Airflow Model Operation mode Fan speed High Cooling ASYG07KETF Quiet ASYG07KETF-B High Heating Quiet High Cooling ASYG09KETF Quiet High ASYG09KETF-B Heating Quiet High Cooling ASYG12KETF Quiet ASYG12KETF-B High Heating Quiet High Cooling ASYG14KETF Quiet High ASYG14KETF-B Heating Quiet - 103 - 8-4.
  • Page 110: Floor Type

    8-5. Floor type Airflow Model Operation mode Fan speed High Cooling Quiet AGYG09KVCA High Heating Quiet High Cooling Quiet AGYG12KVCA High Heating Quiet High Cooling Quiet AGYG14KVCA High Heating Quiet - 104 - 8-5. Floor type 8. Airflow...
  • Page 111: Noise Level Curve

    9. Noise level curve 9-1. Compact cassette type ¢ Model: AUXG07KVLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000...
  • Page 112 ¢ Model: AUXG12KVLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 113: Mini Duct Type

    9-2. Mini duct type ¢ Model: ARXG07KSLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 HIGH NC-35 NC-35 HIGH NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000...
  • Page 114 ¢ Model: ARXG12KSLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency ,Hz Octave band center frequency ,Hz...
  • Page 115: Slim Duct Type

    9-3. Slim duct type ¢ Model: ARXG07KLLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 116 ¢ Model: ARXG12KLLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 HIGH HIGH NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET NC-20 NC-20 QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 117: Wall Mounted Type

    9-4. Wall mounted type ¢ Models: ASYG07KGTB, ASYG07KGTE, and ASYG07KGTF  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 HIGH HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000...
  • Page 118 ¢ Models: ASYG12KGTB, ASYG12KGTE, and ASYG12KGTF  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000...
  • Page 119 ¢ Models: ASYG07KMTB, ASYG07KMCC, ASYG07KMCE, ASYG07KMCF, ASYG07KETA, ASYG07KETA-B, ASYG07KETE, ASYG07KETE-B, ASYG07KETF, and ASYG07KETF-B  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET...
  • Page 120 ¢ Models: ASYG12KMTB, ASYG12KMCC, ASYG12KMCE, ASYG12KMCF, ASYG12KETA, ASYG12KETA-B, ASYG12KETE, ASYG12KETE-B, ASYG12KETF, and ASYG12KETF-B  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET...
  • Page 121: Floor Type

    9-5. Floor type ¢ Model: AGYG09KVCA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 HIGH HIGH NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000...
  • Page 122 ¢ Model: AGYG14KVCA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 HIGH NC-55 NC-55 HIGH NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 123: Sound Level Check Point

    9-6. Sound level check point ¢ Compact cassette type Microphone 1.5 m Microphone - 117 - 9-6. Sound level check point 9. Noise level curve...
  • Page 124 ¢ Mini duct type Measuring duct Measuring duct Set the static pressure as rating in this area Microphone Microphone Side view Front view ¢ Slim duct type Measuring duct Measuring duct Set the static pressure as rating in this area Microphone Microphone Side view...
  • Page 125 ¢ Floor type Microphone Microphone ● ● Airflow Airflow - 119 - 9-6. Sound level check point 9. Noise level curve...
  • Page 126: Electrical Characteristics

    Type Model name area length AUXG07KVLA 0.19 0.15 AUXG09KVLA 0.19 0.15 Compact cassette AUXG12KVLA 0.24 0.19 AUXG14KVLA 0.28 0.22 ARXG07KSLAP 0.33 0.29 ARXG09KSLAP 0.38 0.33 Mini duct ARXG12KSLAP 0.42 0.38 ARXG14KSLAP 0.67 0.58 ARXG07KLLAP 0.41 0.33 ARXG09KLLAP 0.38 0.30...
  • Page 127 Wiring spec. of connection Power supply cable Indoor rated (50 Hz, 230 V) (Indoor unit to outdoor unit) Cross- Limited Input sectional wiring power Type Model name area length ASYG07KETA 0.25 0.20 ASYG07KETA-B ASYG09KETA 0.30 0.24 ASYG09KETA-B ASYG12KETA 0.30 0.24 ASYG12KETA-B ASYG14KETA 0.38...
  • Page 128: Safety Devices

    AUXG07KVLA Activate: 100 ±10°C AUXG09KVLA Fan motor stop Compact cassette AUXG12KVLA Reset: 95 ±10°C AUXG14KVLA Fan motor restart ARXG07KSLAP Activate: 135 ±15°C ARXG09KSLAP Fan motor stop Mini duct ARXG12KSLAP Reset: 115 ±15°C ARXG14KSLAP Fan motor restart 250 V, 5 A ―...
  • Page 129 Terminal Indoor unit Float Model name PCB* fuse Fan motor thermal protector thermal type switch fuse ASYG07KMCC ASYG09KMCC ASYG12KMCC ASYG14KMCC Activate: 170 °C ASYG07KMCE Fan motor stop ASYG09KMCE ― ASYG12KMCE Reset: 145 °C ASYG14KMCE Fan motor restart ASYG07KMCF ASYG09KMCF ASYG12KMCF ASYG14KMCF ASYG07KETA Activate: More than 85°C...
  • Page 130: External Input And Output

    12. External input and output 12-1. Compact cassette, Mini duct, and Slim duct types Exterior of the indoor unit PCB and the component location differ by the type of the indoor unit as follows. • Compact cassette type: Indoor unit PCB CN47 (Ext.
  • Page 131 ¢ External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m. •...
  • Page 132 ¢ Combination of external input and output By combining the function setting of the indoor unit, you can select various combinations of func- tions. Combination examples of external input and output are as follows: External input External output Mode Function setting Terminal CN47 60—00...
  • Page 133 ¢ Details of function  Control input function • When function setting is "Operation/Stop" mode 1 Function setting External input Input signal Command Off → On Operation 46—00 Terminal On → Off Stop Input Operation Indoor unit Stop Remote controller NOTES: •...
  • Page 134 • When function setting is "Operation/Stop" mode 2 Function setting External input Input signal Command Off → On Operation 46—03 Terminal Stop (Remote controller On → Off disabled) Input Operation Indoor unit Stop (R.C. disabled) Remote controller NOTE: When "Operation/Stop" mode 2 function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group.
  • Page 135  Indoor unit fan operation status Function setting External output Output signal Command Low → High Fan run 60—10 CN47 High → Low Fan stop Output signal Condition The indoor unit fan is operating. Low → High The fan is stopped or during cold air prevention. During thermostat off when in dry mode operation.
  • Page 136: 12-2.Wall Mounted Type (Kgtb, Keta, And Keta-B)

    12-2. Wall mounted type (KGTB, KETA, and KETA-B) External input and output PCB SW301 SW302 Rotary switch CN314 CN313 CN312 CN311 CN310 CN308 To CN6 on Indoor unit PCB Input External input External output Connector Input select signal Operation/Stop CN313/ Edge/Pulse Dry contact/ CN314...
  • Page 137 ¢ External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
  • Page 138 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  External Input and Output PCB • A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m. •...
  • Page 139 ¢ Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External Input and Output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input External Input Function...
  • Page 140  Input signal type External Input and Output PCB: The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch SW302 on the External Input and Output PCB. The width of pulse must be longer than 200 msec.
  • Page 141 ¢ Details of function  Control input function • When function setting is "Operation/Stop" mode 1 – In the case of "Edge" input: Rotary SW on Function External Input and External input Input signal Command setting / Output PCB Off → On Operation External Input and 46-00...
  • Page 142 • When function setting is "Forced stop" mode – In the case of "Edge" input: Rotary SW on Function External Input and External input Input signal Command setting / Output PCB Off → On Forced stop External Input and 46-02 60-00 / 1 CN313 Output PCB...
  • Page 143 • When function setting is "Operation/Stop" mode 2 – In the case of "Edge" input: Rotary SW on Function External Input and External input Input signal Command setting / Output PCB Off → On Operation Stop External Input and 46-03 60-00 / 1 CN313 (Remote...
  • Page 144 • Forced thermostat off function Rotary SW on Function External Input and External input Input signal Command setting / Output PCB Thermostat 60-00 / 2 Off → On External Input and Output 60-09 / B CN313 Normal 60-10 / C On →...
  • Page 145  Control output function • Operation/Stop status Rotary SW on Function Output External Input and External output Command setting / signal Output PCB Off → On Operation External Input and Output 60-00 / 1 CN310 On → Off Stop The output is low when the unit is stopped. Operation Indoor unit Stop...
  • Page 146: 12-3.Wall Mounted Type (Kmtb And Kmcc)

    12-3. Wall mounted type (KMTB and KMCC) With using external input and output functions, this product can be operated inter-connectedly with an external device. Connector Input Output Remarks CNA01 Control input — See external input/output CNB01 — Operation status output settings for details.
  • Page 147 • Circuit diagram example • Contact capacity: DC 24 V or more, 10 Indoor unit mA or more. Communication kit Connected unit control PCB • *: Make the distance from the PCB to Example: Switch Connector the connected unit within 10 m. •...
  • Page 148 • Optional part Part name Model name Exterior External input wire External Connect Kit UTY-XWZXZ5 Communication Kit UTY-TWBXF2 * For operating the external function, the wall mounted type requires the communication kit in addi- tion to the wire (UTY-XWZXZ5). - 142 - 12-3.
  • Page 149 ¢ External output With using external output function, operating status of this product can be transmitted to the exter- nal device, and also, this product can be inter-connected with the external device.  Operation status output Air conditioner operation status signal can be output. •...
  • Page 150  Error status output Air conditioner error status signal can be output. • Circuit diagram example: Indoor unit control PCB Communication kit Connected unit Connector DC 24 V Example: Relay unit Example: Display Relay power supply 10 m* Signal Optional parts Locally purchased –...
  • Page 151: 12-4.Wall Mounted Type (Kgte, Kgtf, Kmce, Kmcf, Kete, Kete-B, Ketf, And Ketf-B)

    12-4. Wall mounted type (KGTE, KGTF, KMCE, KMCF, KETE, KETE-B, KETF, and KETF-B) External input and output PCB Indoor unit PCB CN47 (Ext. out) CN65 (Ext. in/out PCB) CN46 (Ext. in) SW301 SW302 Rotary switch CN314 CN313 CN312 CN311 CN310 CN308 Input External input...
  • Page 152 ¢ External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
  • Page 153  External Input and Output PCB The indoor unit Operation/Stop can be set by using the input connector on the PCB. • Input select: Use either one of these types of connectors according to the application. (Both types of connec- tors cannot be used simultaneously.) –...
  • Page 154 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  Indoor unit • A twisted pair cable should be used. Maximum length of cable is 25 m. •...
  • Page 155  External Input and Output PCB • A twisted pair cable should be used. Maximum length of cable is 25 m. • Output voltage: High DC 12 V±2 V, Low 0 V. • Permissible current: 50 mA • For details, refer to "Combination of external input and output"...
  • Page 156 ¢ Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External Input and Output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input Function Rotary...
  • Page 157  Input signal type External Input and Output PCB: The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch SW302 on the External Input and Output PCB. The width of pulse must be longer than 200 msec.
  • Page 158 ¢ Details of function  Control input function • When function setting is “Operation/Stop” mode 1 – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting Input and Output PCB Off → On Operation External Input and 46-00...
  • Page 159 • When function setting is “Forced stop” mode – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting Input and Output PCB Off → On Forced stop External Input and 46-02 CN313 Output PCB On →...
  • Page 160 • When function setting is “Operation/Stop” mode 2 – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting Input and Output PCB Off → On Operation Stop External Input and 46-03 CN313 (Remote Output PCB On →...
  • Page 161 • Forced thermostat off function Rotary SW on Input Function setting / External Input External input Command signal and Output PCB Thermostat 60-00 Off → On External Input and 60-09 CN313 Output PCB Normal On → Off 60-10 operation Input Compressor Room temp.
  • Page 162  Control output function • Operation/Stop status Rotary SW on Output Function setting / External Input External output Command signal and Output PCB 60-00 / 1 Off → On Operation Output of indoor unit CN47 60-00 / 2 On → Off Stop 60-00 / 1 Off →...
  • Page 163 • Indoor unit fan operation status Rotary SW on Output Function setting / External Input External output Command signal and Output PCB Off → On Fan run 60-10 / C Output of indoor unit CN47 On → Off Fan stop 60-00 / 2 Off →...
  • Page 164: 12-5.Floor Type

    12-5. Floor type Indoor unit PCB CN 23 CN 21 CN 15 CN 14 P 190 External input External output Connector Input signal Operation/Stop CN14 Forced stop — Edge Forced thermostat off CN15 Operation status Indoor unit Error status CN20/CN21/ —...
  • Page 165 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  Indoor unit • A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m . •...
  • Page 166 ¢ Combination of external input and output By combining the function setting of the indoor unit, you can select various combinations of func- tions. Combination examples of external input and output are as follows: External input Function Mode Indoor unit setting CN14 CN15...
  • Page 167 ¢ Details of function  Control input function • When function setting is "Operation/Stop" mode 1 – In the case of "Edge" input Mode Function setting External input Input signal Command Off → On Operation — CN14 On → Off Stop 46-00 Input of indoor unit...
  • Page 168 • When function setting is "Operation/Stop"mode 2 – In the case of "Edge" input Mode Function setting External input Input signal Command Off → On Operation Stop — CN14 (Remote On → Off controller disabled) 46-03 Input of indoor unit Off →...
  • Page 169  Control output function • Operation/Stop status Output Mode Function setting External output Command signal Low → High Operation 60-00 CN15 High → Low Stop Output of indoor unit Off → On Operation 60-00 CN20 On → Off Stop The output is low when the unit is stopped. Operation Indoor unit Stop...
  • Page 170 • Indoor unit fan operation status Output Mode Function setting External output Command signal Low → High Fan run 60-10 CN15 High → Low Fan stop Output of indoor unit Off → On Fan run 60-00 CN22 On → Off Fan stop Output signal Condition...
  • Page 171 • Design and install external heater appropriately with considering its protection. • Inappropriate designing and installation of external heater may cause a fire by emitted heat from the external heater. • Fujitsu General Ltd. is not responsible for inappropriate designing or installation of external heating device. - 165 - 12-5.
  • Page 172 • Auxiliary heater control 1 Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode Heater off • Error occurred •...
  • Page 173: Group Connection

    13. Group connection NOTE: Group control cannot be used together with WLAN Adapter. Installation procedure for group control system: A number of indoor units can be operated at the same time using a single remote controller. NOTE: When different type of indoor units (such as wall mounted type and cassette type, cassette type and duct type, or other combinations) are connected using group control system, some functions may no longer be available.
  • Page 174 2. Set the remote controller address. (Function setting) • Addresses will be automatically set when initially starting up this unit. In such a case, do not change the remote controller address for the indoor unit, and keep it at the initial setting of “00”.
  • Page 175: Remote Controller

    14. Remote controller 14-1. Wireless remote controller (AR-REW4E, AR-REM4E, and AR-REB1E) ¢ Overview AR-REW4E Signal transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button...
  • Page 176 To facilitate explanation, the accompanying illustration has been drawn to show all possible indicators; in actual operation, however, the display will only show those indicators appropriate to the current oper- ation. - 170 - 14-1. Wireless remote controller (AR-REW4E, AR-REM4E, and AR-REB1E) 14.
  • Page 177 AR-REM4E Signal SENSOR button transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button SEND button SLEEP button SELECT button RESET button NEXT button...
  • Page 178 AR-REB1E Signal transmitter MODE button FAN button 10°C HEAT button ECONOMY button SWING button OUTDOOR UNIT SET button LOW NOISE button TEMP. button ON TIMER button POWERFUL button OFF TIMER button Start/Stop button TIMER SELECT button RESET button SLEEP TIMER button CLOCK ADJUST button TIMER CANCEL button NOTE: Functions may differ by type of the indoor unit.
  • Page 179 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 180: 14-2.Wireless Remote Controller (Ar-Rew3E)

    14-2. Wireless remote controller (AR-REW3E) ¢ Overview Signal SENSOR button transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button SEND button SLEEP button...
  • Page 181 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 182: 14-3.Wireless Remote Controller (Ar-Rem7E)

    14-3. Wireless remote controller (AR-REM7E) ¢ Overview Signal transmitter MODE button FAN button 10 °C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button SEND button SLEEP button SELECT button...
  • Page 183 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 184: 14-4.Wireless Remote Controller (Ar-Rmb1E)

    14-4. Wireless remote controller (AR-RMB1E) ¢ Overview Signal transmitter MODE button FAN button 10°C HEAT button ECONOMY button SWING button OUTDOOR UNIT SET button LOW NOISE button TEMP. button ON TIMER button POWERFUL button OFF TIMER button Start/Stop button TIMER SELECT button RESET button SLEEP TIMER button TEST RUN button...
  • Page 185 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 186: 14-5.Wireless Remote Controller (Uty-Lnty: Optional Part)

    14-5. Wireless remote controller (UTY-LNTY: Optional part) ¢ Overview Signal transmitter MODE button FAN button 10°C HEAT button TEMP. SWING button button SET button Economy button ON TIMER button OFF TIMER button Start/Stop button REG1U TIMER SELECT button RESET button SLEEP TIMER button TEST RUN button TIMER CANCEL button...
  • Page 187 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 188: 14-6.Ir Receiver Kit With Wireless Remote Controller (Uty-Lbtym: Optional Part)

    14-6. IR receiver kit with Wireless remote controller (UTY- LBTYM: Optional part) ¢ Overview Signal transmitter FAN button MODE button 10°C HEAT button TEMP. SWING button button SET button Economy button ON TIMER button OFF TIMER button Start/Stop button REG1U TIMER SELECT button RESET button SLEEP TIMER button...
  • Page 189 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 190  IR receiver Unit: mm 13.6 57.4 13.6 11.5 18.5 Front view Side view Rear view Size (H × W × D) 145 × 90 × 30 Weight - 184 - 14-6. IR receiver kit with Wireless remote controller (UTY-LBTYM: Optional part) 14.
  • Page 191: 14-7.Wired Remote Controller (Uty-Rnnym: Optional Part)

    14-7. Wired remote controller (UTY-RNNYM: Optional part) ¢ Overview a START/STOP button Starts and stops operation. b SET TEMP. button Selects the setting temperature. c MODE button Selects the operating mode (AUTO , HEAT ,FAN COOL , and DRY d FAN button Selects the fan speed AUTO ,QUIET , LOW...
  • Page 192 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 193 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm Front view Side view Size (H × W × D) 120 × 120 × 18 Weight Cable length (accessory) Power  Wiring specifications Cable size Wire type Remarks Remote controller cable...
  • Page 194  When connecting to Communication Kit (for KM models in Wall mounted type) When connecting the remote controller to optional Communication Kit, follow the procedures men- tioned below. Modify the remote controller cable as follows: • Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
  • Page 195: 14-8.Wired Remote Controller (Uty-Rlry: Optional Part)

    14-8. Wired remote controller (UTY-RLRY: Optional part) ¢ Overview a LED lamp (Operation indicator) Lights while the indoor unit is operating. Blinks when an error occurred. b FAN button Each time the button is pressed, fan speed switches as follows: Auto High Quiet...
  • Page 196 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 197 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm Hole: 9 × 4.5 Hole: 12.5 × 4.5 Hole: 6 × 4.5 Front view Side view Rear view Size (H × W × D) 120 ×...
  • Page 198: 14-9.Wired Remote Controller (Uty-Rvnym: Optional Part)

    14-9. Wired remote controller (UTY-RVNYM: Optional part) ¢ Overview a Display panel (with backlight) b Screen switch button (Left) c Menu button d Cancel button e Cursor button f Screen switch button (Right) g Power indicator h On/off button i Enter button - 192 - 14-9.
  • Page 199 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 200 ¢ Specifications Unit: mm 21.3 Front view Side view Size (H × W × D) 120 × 120 × 21.3 Weight  Wiring specifications Cable size Wire type Remarks Remote controller cable Polar 3 core Use sheathed PVC cable. 0.33 mm - 194 - 14-9.
  • Page 201 ¢ Installation (Remote control main unit) Installation space: Unit : mm or more or more or more 220 or more* NOTE: Secure enough space where a flat-blade screwdriver to remove the case can be inserted. Installation procedures: 1. Process the remote controller cable. Unit : mm 1.
  • Page 202 3. Attach the remote controller. • When attaching to switch box: a. Seal the wiring hole of the remote controller cable. b. Put a remote controller cable through the hole of the rear case. c. Fix the rear case by securing it with attached screws (2 places). •...
  • Page 203 4. Connect the cable to the terminals on the front case. Fix the cable together with the sheath with the cable tie. Cut off the excess cable tie. Tightening torque Terminal screw 0.8 to 1.2 N•m 1. 12V (Red) 2. Signal (White) 3.
  • Page 204 5. Attach the front case. • Insert after adjusting upper part of front case. • When insert the front case, do not pinch the cable. Front case Click! Good Prohibited Prohibited Prohibited CAUTION Insert the upper case firmly. If improperly attached, it will cause the upper case to fall off. ¢...
  • Page 205  When connecting to Communication Kit (for KM models in Wall mounted type) When connecting the remote controller to optional Communication Kit, follow the procedures men- tioned below. Modify the remote controller cable as follows: • Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
  • Page 206: 14-10.Wired Remote Controller (Uty-Rnryz*: Optional Part)

    14-10. Wired remote controller (UTY-RNRYZ*: Optional part) ¢ Overview a Remote temperature sensor (inside) b On/off button Operable only while displaying the “Monitor mode” screen. c LED lamp (operation indicator) d Touch panel display e Set temperature Operating temperature can be set. f Remote controller group name g Mode Operation mode can be set.
  • Page 207 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 208 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. [Unit : mm] 20.4 Model name UTY-RNRYZ* Display 3.8-inch FSTN LCD (255 × 160 dots) with touch panel Dimensions (H × W × D) 120 × 120 × 20.4 Weight Input voltage DC 12...
  • Page 209: 14-11.Wired Remote Controller (Uty-Rcryz1: Optional Part)

    14-11. Wired remote controller (UTY-RCRYZ1: Optional part) ¢ Overview a Display panel b MODE button c Menu button buttons (Set temperature buttons) e FAN button f On/off button g Wireless remote controller signal receiving section - 203 - 14-11. Wired remote controller (UTY-RCRYZ1: Optional part) 14.
  • Page 210 ¢ System diagrams • Single remote control I.U. Remote controller cable A ≤ 500 m ¢ Electrical wiring Indoor unit Remote controller - 204 - 14-11. Wired remote controller (UTY-RCRYZ1: Optional part) 14. Remote controller...
  • Page 211 ¢ Specifications Unit: mm Hole × 2 (for M4 screws) Size (H × W × D) 86 × 86 × 32 Weight  Wiring specifications Cable size Wire type Remarks Remote controller 0.33 to 1.25 mm Non polar 2-core Use sheathed twist pair cable.* cable (22 to 16 AWG) *: Use shielded cable (locally purchased) in accordance with the regional cable standard.
  • Page 212 • Pattern B 1. Use a tool to cut off the terminal on the end of the remote controller cable, and then remove the insulation from the cut end of the cable as shown below. 20 mm Remote controller cable (Non-polar) 2.
  • Page 213: 14-12.Simple Remote Controller (Uty-Rsnym: Optional Part)

    14-12. Simple remote controller (UTY-RSNYM: Optional part) ¢ Overview a START/STOP button Starts and stops operation. b Display backlight button Lights during operation. c Operation lamp Lights during operation. d FAN button Selects the fan speed (AUTO ,HIGH , MED , and QUIET ).
  • Page 214 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 215 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm hole x 2 hole x 2 Front View Side View Rear View Size (H × W × D) 120 × 75 × 14 Weight Cable length (accessory) Power ...
  • Page 216  When connecting to Communication Kit (for KM models in Wall mounted type) When connecting the remote controller to optional Communication Kit, follow the procedures men- tioned below. Modify the remote controller cable as follows: • Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
  • Page 217: 14-13.Simple Remote Controller (Uty-Rsry And Uty-Rhry: Optional Parts)

    14-13. Simple remote controller (UTY-RSRY and UTY-RHRY: Optional parts) ¢ Overview a LED lamp Lights during operation. b Louver button Adjusts the airflow direction. c START/STOP button Starts and stops operation. d FAN control button Switches the fan speed as follows: Auto High Quiet...
  • Page 218 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 219 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm 30.0 30.0 Hole: 9 × 4.5 23.0 Hole: 6 × 4.5 Hole: 12.5 × 4.5 Front View Side View Rear View Size (H × W × D) 120 ×...
  • Page 220: Function Settings

    15. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 15-1. Compact cassette, Mini duct, Slim duct types indoor unit (setting by DIP switch) By using some components on the PCB, you can change the function settings.
  • Page 221 ¢ DIP switch setting • SW100: Remote controller address setting When operating a number of indoor units by using a wired remote controller, DIP switch set- ting for assigning unit number to each indoor unit is required. The slide switches are normally set to make the unit number 00. Remote Switch number controller...
  • Page 222: 15-2.Indoor Unit (Setting By Wireless Remote Controller)

    15-2. Indoor unit (setting by wireless remote controller) CAUTION This setting changes the function settings used to control the indoor unit according to the installa- tion conditions. Incorrect settings can cause a product malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 223 ¢ AR-REM4E (for Wall mounted type KGTB), AR-REW3E (for Wall mounted type KGTE and KGTF), AR-REW4E (for Wall mounted type KETA[-B], KETE[-B], and KETF[-B]), and AR-REM7E (for Floor type)  Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller.
  • Page 224  Function setting procedure Connect the power supply of the outdoor unit. To enter the function setting mode, while holding down the POWERFUL and TEMP. button, press the RESET button. POWERFUL TEMP. ( RESET Function setting mode display Select the function number by pressing the or the buttons.
  • Page 225 Press the MODE button once to transmit the function mode information. Press the button once to transmit the function setting information. 2 short beeps will be emitted from the indoor unit when the signal is received correctly. If wrong code is set, no beep sound will be emitted.
  • Page 226  Resetting the power after setting up all indoor units Important: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
  • Page 227  Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the TEMP.
  • Page 228 ¢ AR-REB1E (for Wall mounted type KMCC) and AR-RMB1E (for Wall mounted type KMCE and KMCF)  Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller. Function number Refer to Function details. Setting number Refer to Function details.
  • Page 229  Function setting procedure Connect the power supply of the outdoor unit. To enter the function setting mode, while holding down the POWERFUL and SET TEMP. buttons, press the RESET button. POWERFUL SET TEMP. ( RESET Function setting mode display Select the function number by pressing the or the buttons.
  • Page 230 Press the MODE button once to transmit the function mode information. 2 short beeps Press the button once to transmit the function setting information. 2 short beeps will be emitted from the indoor unit when the signal is received correctly. If wrong code is set, no beep sound will be emitted.
  • Page 231  Resetting the power after setting up all indoor units Important: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
  • Page 232  Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the SET TEMP.
  • Page 233 ¢ UTY-LNTY (for Compact cassette type) or AR-REJ1E (included in UTY-LBTYM for Duct type)  Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller. Function number Refer to Function details. Setting number Refer to Function details.
  • Page 234  Function setting procedure Connect the power supply of the outdoor unit. To enter the function setting mode, while holding down the ECONOMY and SET TEMP. buttons, press the RESET button. ECONOMY SET TEMP. ( RESET Function setting mode display - 228 - 15-2.
  • Page 235 Select the function number by pressing the or the buttons. Each time the 10°C HEAT button is pressed, it switches between the right digit and the left digit. Change digit Change digit Proceed to the setting number by pressing the ECONOMY button. (To return to the function number selection, press the ECONOMY button again.) Select the function number by pressing the or the...
  • Page 236 Press the button once to transmit the function setting information. 1 short beep will be emit- ted from the indoor unit or the IR receiver when the signal is received correctly. If wrong code is set, no beep sound will be emitted. 1 short beep NOTE: Press button within 30 seconds after pressing MODE button.
  • Page 237  Setting up each indoor unit Repeat step from 1. to 8. to set up each indoor unit. If the custom code is other than " ", steps from 1. to 2. and 8. need to be performed.  Resetting the power after setting up all indoor units Important: •...
  • Page 238  Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the SET TEMP.
  • Page 239: 15-3.Indoor Unit (Setting By Wired Remote Controller)

    15-3. Indoor unit (setting by wired remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 240 ¢ UTY-RNNYM  Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Refer to Function details Remote controller address Setting number Refer to Function details Λ SET TEMP. “V” and “ ”...
  • Page 241 Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit. Not good Good ● Data is not set up on the indoor unit Data is correctly set up on the indoor unit correctly (-- is displayed.) (Flashing display changes to illuminated display.) ●...
  • Page 242 ¢ UTY-RLRY  Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 243 Pressing the "+" or "-" button, to select the function number. Then press the "ENTER" button. Function number Pressing the "+" or "-" button, to select the setting number. Then press the "ENTER" button. Setting number Example: Function number 30 Setting number 01 Error Good...
  • Page 244 ¢ UTY-RVNYM  Function setting procedure Connect the power supply of the outdoor unit. Switch to the function setting mode. When [Menu button] is pressed twice while “Monitor” screen is displayed, it switches to the “Submenu” screen. If [Menu button] is pressed while the “Submenu” screen is displayed, the display returns to the “Monitor”...
  • Page 245 Select the [Function No.] with pressing the [Cursor button (Left/Right)], and select the Function No. to be set with pressing the [Cursor button (Up/Down)]. Function setting Mo 10:00AM R.C. Function Setting address Cancel: Version Error history Select the [Setting No.] with pressing the [Cursor button (Left/Right)], and select the Setting No. to be set with pressing the [Cursor button (Up/Down)].
  • Page 246 When [Cancel button] is pressed twice while “Function setting” screen is displayed, it switches to the “Submenu” screen. Function setting Mo 10:00AM R.C. Function Setting Submenu Mo 10:00AM address Date and time Screen Cancel: Filter sign Version Error history R.C. sensor control Room temp.
  • Page 247 ¢ UTY-RNRYZ*  Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 248 “Function No.” screen is displayed. Set the “Function No.” with Function No. Cancel When the “OK” is touched, the display returns to the “Function Setting” screen. Touch the “Function No.” on the “Function Setting” screen. Function Setting Address [002–01] Function No. [30] Setting No.
  • Page 249 Touch the “Yes” of the verification screen. Function Setting Function setting will be performed. OK? In case of “ERROR” In case of “OK” Function Setting Function Setting Address [002–01] Address [002–01] Function No. [30] Function No. [30] Setting No. [01] Setting No.
  • Page 250: 15-4.Indoor Unit (Setting By Simple Remote Controller)

    15-4. Indoor unit (setting by simple remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 251 ¢ UTY-RSNYM  Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Setting number Refer to Function details Refer to Function details Remote controller address START/STOP button Transmits function setting FAN button SET TEMP.
  • Page 252 Select the setting number by pressing the SET TEMP. or SET TEMP. button. The setting number indicator flashes during setting number selection. Setting number Example) Function number : 30, Setting number : 01 Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit.
  • Page 253  Resetting the power after setting up function of all indoor units NOTES: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
  • Page 254 ¢ UTY-RSRY/UTY-RHRY  Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 255 Select the item number to be set with the SET TEMP. or SET TEMP. button, and press button to switch to the setting screen. Select the “13” in Menu 2-F1 settings. Then, press the button. Select the 2-wire remote controller address with the SET TEMP. or SET TEMP.
  • Page 256 Setting results are displayed after data transmission. Press the button to return to the 2-wire remote controller address selection screen of step 9. If setting has been completed, press the FAN button to return to the Menu 2-F1 item se- lection screen.
  • Page 257: 15-5.Function Details

    15-5. Function details ¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected.  Function setting list Functio Functions Compact cassette...
  • Page 258 Wall mounted Functio Functions n no. KGTB KGTE KGTF KMTB KMCC Remote controller ● — — ● ● address setting Filter sign ● ● ● ● ● Ceiling height — — — — — Outlet directions — — — — —...
  • Page 259 1) Remote controller address setting (for Wall-mounted type only) NOTES: • Because this setting is normally done automatically when 2-wire-type wired remote controller is installed, setting is unnecessary. • This setting is configurable only by wireless remote controller, but not configurable by Polar 3- wired remote controller.
  • Page 260 3) Ceiling height (for Compact cassette type only) Select the appropriate ceiling height according to the place of installation. Function number Setting value Setting description Factory setting Standard ♦ High ceiling For the specific height for each setting value, refer to “Installation space” in Chapter 4. "Dimensions"...
  • Page 261 5) Static pressure (for Mini duct type and Slim duct type) Select the appropriate static pressure according to the installation conditions. For mini duct type: Function number Setting value Setting description Factory setting 0 Pa 10 Pa 20 Pa 30 Pa 40 Pa 50 Pa Standard...
  • Page 262 6) Room temperature control for indoor unit sensor (for other than Floor type) NOTE: If the remote sensor unit option is selected, perform this setting. Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature of the room temperature sensor is corrected as follows: Corrected temp.
  • Page 263 7) Room temperature control for wired remote controller sensor (for other than Floor type) Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
  • Page 264 10) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 11) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description...
  • Page 265 14) Switching functions for external output terminal (For other than KETA[-B] models in Wall- mounted type) Functions of the external output terminal can be switched. For details, refer to “External input and output”. Function number Setting value Setting description Factory setting Operation status ♦...
  • Page 266: 15-6.Wired Remote Controller (Uty-Rnnym)

    15-6. Wired remote controller (UTY-RNNYM) Prohibited Dual remote controller setting Prohibited DIP switch 1 °F/°C switch Prohibited Memory backup setting * Do not use DIP switch 2. ¢ Switch location Front case (back side) DIP switch 2 DIP switch 1 ¢...
  • Page 267  SW6: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure. Memory backup Factory setting Disable ♦...
  • Page 268: 15-7.Wired Remote Controller (Uty-Rvnym)

    15-7. Wired remote controller (UTY-RVNYM) Memory backup setting DIP switch 1 Dual remote controller setting ¢ Switch location ¢ DIP switch setting  SW1: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure.
  • Page 269: 15-8.Wired Remote Controller (Uty-Rlry)

    15-8. Wired remote controller (UTY-RLRY) DIP switch Memory backup setting ¢ Switch location Front case (back side) Set the DIP switch to ON ¢ Dip switch setting  SW1: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure.
  • Page 270: 15-10.Simple Remote Controller (Uty-Rsnym)

    15-10. Simple remote controller (UTY-RSNYM) Prohibited Dual remote controller setting °F/°C switch DIP switch Prohibited Prohibited Prohibited ¢ Switch location DIP Switch ¢ DIP switch setting  SW2: Dual remote controller setting Set the remote controller SW2 according to the following table. Primary unit Secondary unit Number of remote controller...
  • Page 271: Accessories

    16. Accessories 16-1. Compact cassette type ¢ Models: AUXG07–14KVLA Part name Exterior Part name Exterior Operation manual Drain hose insulation Operation manual Hose band (CD-ROM) Coupler heat insulation Installation manual (large) Coupler heat insulation Template (Carton top) (small) M10 nut A Cable tie (with flange) M10 nut B...
  • Page 272: 16-2.Mini Duct Type

    16-2. Mini duct type ¢ Models: ARXG07–14KSLAP Part name Exterior Part name Exterior Operation manual Drain hose Operation manual Hose band (CD-ROM) Installation manual Drain hose insulation B Installation template Washer (Carton top) Coupler heat insulation Cable tie (large) (large) Coupler heat insulation Cable tie (medium) (small)
  • Page 273: 16-3.Slim Duct Type

    16-3. Slim duct type ¢ Models: ARXG07–14KLLAP Part name Exterior Part name Exterior Operation manual Filter (small) Operation manual Drain hose (CD-ROM) Installation manual Hose band Installation template Drain hose insulation B Insulation Washer (for electrical wiring) Coupler heat insulation Cable tie (large) (large) Coupler heat insulation...
  • Page 274: 16-4.Wall Mounted Type

    16-4. Wall mounted type ¢ Models: ASYG07–14KGTB, ASYG07–14KMTB, and ASYG07– 14KMCC Part name Exterior Part name Exterior Operation manual Cloth tape Operation manual Self-tapping screw (CD-ROM) (large) Self-tapping screw Installation manual (small) Remote controller Wall hook bracket Battery Filter holder Remote controller Air cleaning filters holder...
  • Page 275 ¢ Models: ASYG07–14KGTE and ASYG07–14KGTF Part name Exterior Part name Exterior Operation manual Cloth tape Operation manual Self-tapping screw (CD-ROM) (large) Self-tapping screw Installation manual (small) Remote controller Wall hook bracket Battery Filter holder Remote controller Air cleaning filters holder - 269 - 16-4.
  • Page 276 ¢ Models: ASYG07–14KMCE and ASYG07–14KMCF Part name Exterior Part name Exterior Operation manual Cloth tape Operation manual Self-tapping screw (CD-ROM) (large) Self-tapping screw Installation manual (small) Remote controller Wall hook bracket Battery Filter holder Remote controller Air cleaning filters holder - 270 - 16-4.
  • Page 277 ¢ Models: ASYG07–14KETA, ASYG07–14KETA-B, ASYG07– 14KETE, ASYG07–14KETE-B, ASYG07–14KETF, and ASYG07– 14KETF-B Part name Exterior Part name Exterior Operation manual Cloth tape Operation manual Self-tapping screw (CD-ROM) (large) Self-tapping screw Installation manual (small) Remote controller Wall hook bracket Battery Filter holder Remote controller Air cleaning filters holder...
  • Page 278: 16-5.Floor Type

    16-5. Floor type ¢ Models: AGYG09–14KVCA Part name Exterior Part name Exterior Operation manual (CD- Operation manual ROM) Installation manual Cloth tape Self-tapping screws Wall hook bracket (large) Self-tapping screws Remote controller (small) Battery Air cleaning filters Remote controller holder - 272 - 16-5.
  • Page 279: Optional Parts

    17. Optional parts 17-1. Controllers ¢ Lineup Type Indoor unit type Wireless Remote Controller AR-REM4E AR-REM7E AR-REB1E Compact cassette — — — Mini duct — — — Slim duct — — — KGTB ● — — KGTE — — — KGTF —...
  • Page 280 Type Indoor unit type Wired Remote Controller UTY-RNNYM UTY-RVNYM UTY-RLRY UTY-RNRYZ* UTY-RCRYZ1 Compact cassette ◌ ◌ ◌ ◌ ◌ Mini duct ◌ ◌ ◌ ◌ ◌ Slim duct ◌ ◌ ◌ ◌ ◌ KGTB — — ◌ ◌ ◌ KGTE —...
  • Page 281 ¢ Parts Exterior Part name Model name Summary Easy finger touch operation with LCD panel. Backlit LCD enables easy Wired Remote UTY-RNRYZ* operation in a dark room. Controller Wire type: Non-polar 2-wire High visibility and easy operation. Room temperature can be accurately Wired Remote UTY-RLRY controlled using the thermo sensor.
  • Page 282 Exterior Part name Model name Summary Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, temperature setting, and operation Simple Remote UTY-RSNYM Controller mode. Wire type: Polar 3-wire IR Receiver Kit Unit control is performed by Wireless with Wireless UTY-LBTYM Remote Controller...
  • Page 283: 17-2.Cassette Grille

    17-2. Cassette grille ¢ Lineup Indoor unit type Model Compact cassette UTG-UFYF-W ¢ Part Exterior Part name Model name Summary This cassette grille can be installed Cassette Grille UTG-UFYF-W appropriately on the grid type ceiling common in the office. - 277 - 17-2.
  • Page 284: 17-3.Others

    17-3. Others ¢ Lineup Type Air Outlet Shutter Insulation Kit for Fresh Air Intake Half Concealed Indoor unit type Plate High Humidity UTR-YDZB UTZ-KXGC UTZ-VXAA UTR-STA Compact cassette ◌ ◌ ◌ — Mini duct — — — — Slim duct —...
  • Page 285 Type External Input and Output Indoor unit type External Connect Kit UTY-XWZX UTY-XWZXZ5 UTY-XWZXZG UTY-XCSXZ2 UTY-XCSX Compact cassette — — ◌ — ◌ Mini duct — — ◌ — — Slim duct — — ◌ — — KGTB ◌ — —...
  • Page 286 Type Air Cleaning Indoor unit type Communication Kit Filter UTY-TWBXF2 UTY-TWRXZ2 UTY-TWRXZ3 UTR-FA16-5 Compact cassette — — — — Mini duct — — — — Slim duct — — — — KGTB — ◌ — — KGTE — ◌ — —...
  • Page 287 ¢ Parts Exterior Part name Model name Summary Thermo-sensor for sensing the Remote Sensor UTY-XSZX temperature of arbitrary place in the Unit room. Width: 683 mm For 07, 09, 12, and 14 models Auto Louver UTD-GXTA-W Grille Kit Air Cleaning Air Cleaning Filter can be mounted to UTR-FA16-5 Filter...
  • Page 288 Exterior Part name Model name Summary Use to connect with external devices and air conditioner PCB. External Input UTY-XCSX and Output PCB Optional External Connect Kit is necessary for installation. Use to connect with external devices and air conditioner PCB. External Input UTY-XCSXZ2 and Output PCB...
  • Page 289 Exterior Part name Model name Summary For connection between indoor unit with UART interface and a KNX open KNX Convertor UTY-VKSX network. This converter is required when Network connecting single split system to VRF UTY-VTGX Converter network system. Network This converter is required when Converter connecting single split system to VRF UTY-VTGXV...
  • Page 290: Indoor Unit Installation Precautions

    18. Indoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 18-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.
  • Page 291 Condition Contents Countermeasures (Reference) When inside the When the indoor unit is installed where the inside of the 1. Add heat insulating material to ceiling is high ceiling is 30 °C RH80% or greater, the dew point the outside of the indoor unit temperature temperature of the outer perimeter may become higher cabinet.
  • Page 292 Condition which requires addition of outside heat insulation Relative humidity 80 % Dry bulb temperature 30 °C Figure 18-1 Moist air curve Slit of heat insulating material Heat insulation reinforcement material Flare connection facing upward (locally purchased) To indoor unit Covered gas pipe (heat insulation...
  • Page 293: Part 2. Outdoor Unit (2 Units Type)

    Part 2. OUTDOOR UNIT (2 UNITS TYPE) MULTI-SPLIT TYPE: AOYG14KBTA2 AOYG18KBTA2...
  • Page 294: Specifications

    1. Specifications Type Inverter heat pump Model name AOYG14KBTA2 AOYG18KBTA2 Power source 230 V 50 Hz Available voltage range 198—264V Wall mounted Wall mounted Standard combination of indoor unit ASYG07KGTB ×2 ASYG09KGTB ×2 Rated Btu/h 13,600 17,100 Cooling 1.4—4.6 1.7—5.8 Min.—Max.
  • Page 295 Specifications for ErP Lot10 Model name AOYG14KBTA2 AOYG18KBTA2 Cooling Energy efficiency class Heating (Average) Cooling 4.0 (35 °C) 5.0 (35 °C) Pdesign Heating (Average) 3.5 (-10 °C) 4.2 (-10 °C) SEER Cooling 8.70 8.60 kWh/kWh SCOP Heating (Average) 4.70 4.70 Annual energy consumption kWh/a QHE (Average)
  • Page 296: Dimensions

    2. Dimensions 2-1. Model: AOYG14KBTA2 Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow 19.7 Drain port Ø42 150.1 Bottom view Side view (Valve part) - 290 - 2-1. Model: AOYG14KBTA2 2.
  • Page 297: Model: Aoyg18Kbta2

    2-2. Model: AOYG18KBTA2 Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow 19.7 Drain port Ø42 150.1 Bottom view Side view (Valve part) - 291 - 2-2. Model: AOYG18KBTA2 2. Dimensions...
  • Page 298: Installation Space

    3. Installation space 3-1. Models: AOYG14KBTA2 and AOYG18KBTA2 ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
  • Page 299  Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
  • Page 300  Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
  • Page 301: Refrigerant Circuit

    4. Refrigerant circuit 4-1. Model: AOYG14KBTA2 - 295 - 4-1. Model: AOYG14KBTA2 4. Refrigerant circuit...
  • Page 302: Model: Aoyg18Kbta2

    4-2. Model: AOYG18KBTA2 - 296 - 4-2. Model: AOYG18KBTA2 4. Refrigerant circuit...
  • Page 303: Wiring Diagram

    5. Wiring diagram 5-1. Model: AOYG14KBTA2 - 297 - 5-1. Model: AOYG14KBTA2 5. Wiring diagram...
  • Page 304: Model: Aoyg18Kbta2

    5-2. Model: AOYG18KBTA2 - 298 - 5-2. Model: AOYG18KBTA2 5. Wiring diagram...
  • Page 305: Capacity Table

    6. Capacity table 6-1. Combinations ¢ Model: AOYG14KBTA2  Cooling Rated capacity for Combination of indoor Total capacity each indoor unit Input power (kW) Seasonal data unit (kW) (kW) (W/W) Unit Unit Pdesign SEER Energy effi- Total Min. Rated Max. Min.
  • Page 306 ¢ Model: AOYG18KBTA2  Cooling Rated capacity for Combination of in- Total capacity each indoor unit Input power (kW) Seasonal data door unit (kW) (kW) (W/W) Unit Unit Pdesign SEER Energy efficien- Total Min. Rated Max. Min. Rated Max. (kW) (kWh/kWh) cy class 2.00...
  • Page 307: Cooling Capacity

    6-2. Cooling capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOYG14KBTA2 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB...
  • Page 308  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.80 1.22 2.04 1.39 2.15 1.60 2.30 1.79 2.46 1.96...
  • Page 309  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.80 1.25 2.04 1.42 2.15 1.64 2.30 1.84...
  • Page 310  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.80 1.25 2.04 1.42 2.15 1.64 2.30 1.84 2.46 2.01...
  • Page 311  Wall mounted type Models: ASYG07KGTB, ASYG07KGTE, and ASYG07KGTF Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.80 1.01 2.04 1.16 2.15 1.33 2.30...
  • Page 312 Models: ASYG07KMTB, ASYG07KMCC, ASYG07KMCE, and ASYG07KMCF Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.80 1.01 2.04 1.16 2.15 1.33 2.30 1.50 2.46 1.64...
  • Page 313 Models: ASYG07KETA, ASYG07KETA-B, ASYG07KETE, ASYG07KETE-B, ASYG07KETF, and ASYG07KETF-B Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.80 1.01 2.04 1.16 2.15 1.33 2.30 1.50...
  • Page 314  Floor type Model: AGYG09KVCA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 2.03 1.39 2.29 1.58 2.42 1.82 2.59 2.05 2.77 2.24 2.85...
  • Page 315 ¢ Model: AOYG18KBTA2 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 0.80 0.81 0.82 0.83...
  • Page 316 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 0.63 0.64 0.65 0.65 0.66 0.67 0.82...
  • Page 317  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.32 2.22 1.51 2.34 1.74 2.50 1.95 2.67 2.13...
  • Page 318  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.36 2.22 1.55 2.34 1.78 2.50 2.00...
  • Page 319  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.36 2.22 1.55 2.34 1.78 2.50 2.00 2.67 2.19...
  • Page 320  Wall mounted type Models: ASYG07KGTB, ASYG07KGTE, and ASYG07KGTF Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50...
  • Page 321 Models: ASYG07KMTB, ASYG07KMCC, ASYG07KMCE, and ASYG07KMCF Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78...
  • Page 322 Models: ASYG07KETA, ASYG07KETA-B, ASYG07KETE, ASYG07KETE-B, ASYG07KETF, and ASYG07KETF-B Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63...
  • Page 323  Floor type Model: AGYG09KVCA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 2.51 1.71 2.84 1.95 2.99 2.25 3.20 2.53 3.42 2.76 3.53...
  • Page 324: Heating Capacity

    6-3. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOYG14KBTA2 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 3.30...
  • Page 325  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.67 1.63 1.59 1.55 1.51 -10.0 -11.0 1.88 1.84 1.79 1.75 1.70 -5.0 -7.0 2.10 2.05 2.00 1.95 1.90 -2.0 2.66 2.60 2.54...
  • Page 326  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.67 1.63 1.59 1.55 1.51 -10.0 -11.0 1.88 1.84 1.79 1.75 1.70 -5.0 -7.0 2.10 2.05 2.00 1.95 1.90 -2.0 2.66...
  • Page 327  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.67 1.63 1.59 1.55 1.51 -10.0 -11.0 1.88 1.84 1.79 1.75 1.70 -5.0 -7.0 2.10 2.05 2.00 1.95 1.90 -2.0 2.66 2.60 2.54...
  • Page 328  Wall mounted type Models: ASYG07KGTB, ASYG07KGTE, and ASYG07KGTF Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.67 1.63 1.59 1.55 1.51 -10.0 -11.0 1.88 1.84 1.79 1.75 1.70 -5.0 -7.0 2.10 2.05 2.00 1.95 1.90 -2.0...
  • Page 329 Models: ASYG07KMTB, ASYG07KMCC, ASYG07KMCE, and ASYG07KMCF Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.67 1.63 1.59 1.55 1.51 -10.0 -11.0 1.88 1.84 1.79 1.75 1.70 -5.0 -7.0 2.10 2.05 2.00 1.95 1.90 -2.0 2.66 2.60 2.54...
  • Page 330 Models: ASYG07KETA, ASYG07KETA-B, ASYG07KETE, ASYG07KETE-B, ASYG07KETF, and ASYG07KETF-B Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.67 1.63 1.59 1.55 1.51 -10.0 -11.0 1.88 1.84 1.79 1.75 1.70 -5.0 -7.0 2.10 2.05 2.00 1.95 1.90 -2.0 2.66...
  • Page 331  Floor type Model: AGYG09KVCA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.87 1.83 1.79 1.74 1.70 -10.0 -11.0 2.12 2.07 2.02 1.96 1.91 -5.0 -7.0 2.36 2.30 2.24 2.19 2.13 -2.0 2.99 2.92 2.85 2.78...
  • Page 332 ¢ Model: AOYG18KBTA2 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 1.63 1.67 1.70 1.73 1.77 -10.0 -11.0 1.68 1.72 1.75 1.79 1.82 -5.0 -7.0 1.73 1.76 1.80...
  • Page 333 NOTES: • TC: Total Capacity (kW), IP: Input Power (kW) • Values mentioned in the table are based on the following conditions: – Power source of specifications: 230 V – Pipe length: 5 m, Height difference: 0 m (Outdoor unit—Indoor unit) •...
  • Page 334  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.58 1.55 1.51 1.47 1.43 -10.0 -11.0 1.82 1.78 1.74 1.69 1.65 -5.0 -7.0 2.06 2.01 1.96 1.91 1.86 -2.0 2.63 2.56 2.50...
  • Page 335  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.58 1.55 1.51 1.47 1.43 -10.0 -11.0 1.82 1.78 1.74 1.69 1.65 -5.0 -7.0 2.06 2.01 1.96 1.91 1.86 -2.0 2.63...
  • Page 336  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.58 1.55 1.51 1.47 1.43 -10.0 -11.0 1.82 1.78 1.74 1.69 1.65 -5.0 -7.0 2.06 2.01 1.96 1.91 1.86 -2.0 2.63 2.56 2.50...
  • Page 337  Wall mounted type Models: ASYG07KGTB, ASYG07KGTE, and ASYG07KGTF Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.58 1.55 1.51 1.47 1.43 -10.0 -11.0 1.82 1.78 1.74 1.69 1.65 -5.0 -7.0 2.06 2.01 1.96 1.91 1.86 -2.0...
  • Page 338 Models: ASYG07KMTB, ASYG07KMCC, ASYG07KMCE, and ASYG07KMCF Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.58 1.55 1.51 1.47 1.43 -10.0 -11.0 1.82 1.78 1.74 1.69 1.65 -5.0 -7.0 2.06 2.01 1.96 1.91 1.86 -2.0 2.63 2.56 2.50...
  • Page 339 Models: ASYG07KETA, ASYG07KETA-B, ASYG07KETE, ASYG07KETE-B, ASYG07KETF, and ASYG07KETF-B Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.58 1.55 1.51 1.47 1.43 -10.0 -11.0 1.82 1.78 1.74 1.69 1.65 -5.0 -7.0 2.06 2.01 1.96 1.91 1.86 -2.0 2.63...
  • Page 340  Floor type Model: AGYG09KVCA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 2.04 1.99 1.94 1.89 1.84 -10.0 -11.0 2.34 2.29 2.23 2.18 2.12 -5.0 -7.0 2.65 2.59 2.52 2.46 2.40 -2.0 3.38 3.30 3.22 3.14...
  • Page 341: Capacity Compensation Rate For Pipe Length And Height Difference

    7. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 7-1. Model: AOYG14KBTA2 NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 342 ¢ Indoor unit: 9,000 Btu/h Pipe length Cooling — — — 0.924 0.891 — — 0.962 0.931 0.899 Indoor unit is higher than outdoor unit *1 — 0.991 0.968 0.938 0.905 0.993 0.993 0.970 0.940 0.907 1.000 1.000 0.977 0.946 0.913 -2.5 1.000...
  • Page 343: Model: Aoyg18Kbta2

    7-2. Model: AOYG18KBTA2 NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Indoor unit: 7,000 Btu/h Pipe length Cooling — — — 0.940 0.914 — — 0.973 0.948 0.921 Indoor unit is higher than outdoor unit *1 —...
  • Page 344 ¢ Indoor unit: 12,000 Btu/h Pipe length Cooing — — — 0.919 0.883 — — 0.962 0.926 0.891 Indoor unit is higher than outdoor unit *1 — 0.991 0.969 0.933 0.897 0.993 0.993 0.971 0.935 0.899 1.000 1.000 0.978 0.941 0.905 -2.5 1.000...
  • Page 345: Additional Charge Calculation

    8. Additional charge calculation 8-1. Model: AOYG14KBTA2 Refrigerant type Refrigerant amount ¢ Refrigerant charge Total pipe length 20 or less 30 (Max.) 20 g/m Additional charge 8-2. Model: AOYG18KBTA2 Refrigerant type Refrigerant amount 1,020 ¢ Refrigerant charge Total pipe length 20 or less 30 (Max.) 20 g/m...
  • Page 346: Airflow

    9. Airflow 9-1. Model: AOYG14KBTA2  Cooling 1,670  Heating 1,670 9-2. Model: AOYG18KBTA2  Cooling 1,960 1,154  Heating 2,020 1,189 - 340 - 9-1. Model: AOYG14KBTA2 9. Airflow...
  • Page 347: Operation Noise (Sound Pressure)

    10. Operation noise (sound pressure) 10-1. Noise level curve ¢ Model: AOYG14KBTA2  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000...
  • Page 348: 10-2.Sound Level Check Point

    10-2. Sound level check point Rear Microphone Microphone Airflow Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above. - 342 - 10-2. Sound level check point 10. Operation noise (sound pressure)
  • Page 349: Electrical Characteristics

    11. Electrical characteristics Model name AOYG14KBTA2 AOYG18KBTA2 Voltage 230 ~ Power supply Frequency 10.9 11.6 Maximum operating current * Starting current Main fuse (Circuit breaker) current Power cable Wiring spec. * Connection Cross-sectional area cable * Limited wiring length : Maximum operating current is the total current of the indoor unit and the outdoor unit. : Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
  • Page 350: Safety Devices

    12. Safety devices Model Type of Protection form protection AOYG14KBTA2 AOYG18KBTA2 250 V, 5 A 250 V, 5 A Current fuse Circuit protection 250 V, 20 A 250 V, 25 A (Main PCB) 250 V, 3.15 A 250 V, 3.15 A 127 ±5 °C 125 ±10 °C Activate...
  • Page 351: Accessories

    13. Accessories 13-1. Models: AOYG14KBTA2 and AOYG18KBTA2 Part name Exterior Part name Exterior Installation manual Drain pipe - 345 - 13-1. Models: AOYG14KBTA2 and AOYG18KBTA2 13. Accessories...
  • Page 352: Outdoor Unit Installation Precautions

    14. Outdoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 14-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.