Warren Controls AmurAct Linkage LS Series Installation, Operation And Maintenance Instructions

With f3, f4, f5, & f6 motors

Advertisement

Quick Links

LS & LE LINKAGES with F3, F4, F5, & F6 MOTORS
PRODUCT OVERVIEW
The AmurAct actuator is a fast stroking industrial electric actuator
mated to four different series of industrial control valves ranging in
size from ½" to 4" depending on series and profile. The new generation
of Motors covered in this IOM allow the user to select either a linear
stem lift or a non-linear stem lift by means of a dipswitch. Linear stem
lift is the factory default dipswitch selection. Linear stem lift means
the stem position is linear with respect to the input signal. For exam-
ple if the valve is closed with a 0% input signal, the valve will be at 25%
Stroke with a 25% input signal, at 50% Stroke with a 50% input signal,
at 75% Stroke with a 75% input signal, and at 100% Stroke with a 100%
input signal. Linear stem lift preserves the inherent flow characteristic
of the valve. This feature is applicable only to 2-way valves.
APPLICATIONS & KEY FEATURES
This product serves a variety of applications very well but is particu-
larly well suited to semi-instantaneous water heaters, heat exchangers
and coils where response times to load changes are expected to be
handled in two to three seconds. With the High Temperature LE link-
age option, thermal fluids, superheated steam and high temperature
hot water are safely served. With the NEMA 4X Option, many hose
down and outdoor applications are possible.
AMURACT ACTUATORS
Installation Operation and Maintenance Instructions

TABLE OF CONTENTS

Overview ..................................................Cover
Description .......................................................2
Theory of Operation ......................................3
Safety Precautions..........................................4
Wiring & Dipswitch Settings ...................5-7
Initial Start-up and Operation ....................8
Standard vs High Temperature ..................9
Remove Motor .................................................9
Troubleshooting .......................................... 15
Operating Tips .............................................. 15
Typical Assembly Drawings ...............16-23
When non-linear stem lift is selected the actuator has an ever gain
changing stroke curve that accelerates in the last half of the stroke
and is relatively slow on startup. Extreme gain changes as present in
the Non- liner configuration are difficult for a control system to man-
age. If an application's turndown requirements are only 3:1 to 5:1 for
example such that a valve could be sized to only operate from 50%
to 100% of stroke, some level of speed of response can be achieved
in the Non-linear configuration. The non-linear configuration is appli-
cable to 3-way valves. Otherwise, in all other circumstances, the Linear
Stem Lift (factory default) will be the desired setting.
In either case, correct control valve sizing is critical to good operation.
See individual product specifications for details on the control valve
assemblies and Cv tables. This document will focus on the installation,
operation, and maintenance of the actuator portion only.
* Enerdrive® Failsafe System for Fail Close or Open (selectable)
* Full Range of AC and DC Voltage Supplies Available
* Universal Input (Voltage or Milliamp) and pushbutton stroke
calibration
* All Stainless Steel Linkage Construction with maintenance free
Oilite® bearings

Advertisement

Table of Contents
loading

Summary of Contents for Warren Controls AmurAct Linkage LS Series

  • Page 1: Table Of Contents

    AMURACT ACTUATORS LS & LE LINKAGES with F3, F4, F5, & F6 MOTORS Installation Operation and Maintenance Instructions TABLE OF CONTENTS Overview ..........Cover Description ............2 Theory of Operation ........3 Safety Precautions..........4 Wiring & Dipswitch Settings ....5-7 Initial Start-up and Operation ....8 Standard vs High Temperature ....9 Remove Motor ..........9 Remove/Install/Calibrate Linkage ...11-14...
  • Page 2: Description

    DESCRIPTION The AmurAct actuation system is comprised of two principal age converts rotary force and motion to linear force and motion components. The first is an electrical/electronic motor, which to operate the reciprocating stem of an attached globe-style produces torque (rotational force) and applies it to the input valve.
  • Page 3: Theory Of Operation

    THEORY OF OPERATION Refer to page 2 and below for identification and location of draws the VALVE STEM upward. The articulated link connection components and parts. reduces side loading on the valve stem packing. Raising the stem of a two-way valve opens it. Raising the stem of a three-way valve opens Four AmurAct MOTORS are available: the F3 and F5 produce 120 the lower (L) port and shuts the upper (U) port.
  • Page 4: Safety Precautions

    STOP READ ALL OF THE FOLLOWING SAFETY PRECAUTIONS BEFORE PROCEEDING! SAFETY PRECAUTIONS READ THIS PAGE BEFORE PROCEEDING! Good engineering practice dictates that isolation valves must be installed in inlet and outlet piping connected to the AmurAct control valve. A means should be provided to de-pressurize line media trapped between them when they are shut. Pressure can cause the valve stem and any attached mechanism to move with force, posing a threat to safety.
  • Page 5: Wiring & Dipswitch Settings

    WIRING & STARTING AN AMURACT CONTROL VALVE This applies to all AmurAct models. 50VA. The Power Supply wires if not Contact the factory at (610) 317-0800 Remove the screw from the black mo- specified should be a minimum of 18 tor cover and refer to the following AWG and at that gauge should not ex- before attempting to reconfigure or...
  • Page 6 WIRING SUPPLY, SIGNAL AND FEEDBACK SUPPLY VOLTAGE F3 & F4 MOTORS 120 VAC (SINGLE-PHASE 50/60 HZ) Locate the green case-grounding wire inside the motor case and connect it to the earth ground lead from the power source. Connect the neutral NEUTRAL (typically white) wire to terminal one (1) on terminal block TB4.
  • Page 7 CONFIGURATION OF DIPSWITCHES Factory default configuration of the five dipswitches is shown below. DIPSWITCHES Switch #1: Action & Switch #1 Factory default - ON An increasing control Signal Loss signal causes the valve stem to drive up, opening Switch #2: Power Fail a two-way valve, or opening the L (lower) port and Switch #3: Signal closing the U (upper) port of a three-way valve.
  • Page 8: Initial Startup And Operation

    INITIAL STARTUP AND OPERATION EXTENDED STANDARD TO RE-ORIENT THE AMURACT ON THE VALVE LINKAGE LINKAGE CONSULT FACTORY If it is necessary to re-position AmurAct on the valve call the factory at 610-317-0800 for procedural assistance. FAILURE TO DO SO WILL VOID THE WARRANTY COVERAGE.
  • Page 9: Standard Vs High Temperature

    STANDARD VS HIGH TEMPERATURE LINKAGE IF IT IS NECESSARY TO RE-POSITION AMURACT ON THE VALVE CALL THE FACTORY AT 610-317-0800 FOR PROCEDURAL ASSISTANCE. FAILURE TO DO SO WILL VOID THE WARRANTY COVERAGE. The AmurAct is available with For higher temperature applica- two versions of Linkage.
  • Page 10 MOTOR INSTALLATION AND CALIBRATION The Enerdrive energy must be dissipated before completing these steps. See Removing on AmurAct motor Step 3. Slide the motor output clamp over the linkage shaft; then install the anti-rotation screw, securing it with its locking nut. The Anti-Rotation Screw to the Motor Tab should have some play.
  • Page 11: Remove/Install/Calibrate Linkage

    REMOVING/INSTALLING/CALIBRATING AN AMURACT LINKAGE There are currently three ways in which AmurAct linkages are employed. It is necessary to identify which version is applicable before proceeding. VERSION A: Two-way valves with ¾” stem travel. This applies to all two-way AmurAct control valves, with the exception of: VERSION B: Two-way valves with 1 1/8”...
  • Page 12 CALIBRATING THE AMURACT LINKAGE OVERVIEW: Calibration of the AmurAct linkage is accomplished by adjusting WARNING effective stem length so the linkage crank is precisely aligned with a benchmark when the valve plug contacts the valve seat. Precision is necessary, because the remaining crank travel determines how much force will be applied to the valve plug to achieve tight shutoff.
  • Page 13 CALIBRATING THE AMURACT LINKAGE OVERVIEW: Calibration of the AmurAct linkage is accomplished by adjusting effec- WARNING tive stem length so the linkage crank is precisely aligned with a benchmark when the valve plug contacts the valve seat. Precision is necessary, because the remaining crank travel determines how much force will be applied to the valve plug to achieve The valve stem must be raised when making stem connector tight shutoff.
  • Page 14 CALIBRATING THE AMURACT LINKAGE OVERVIEW: Calibration of the AmurAct linkage is accomplished by adjusting effec- WARNING tive stem length so the linkage crank is precisely aligned with a benchmark when the valve plug contacts the valve seat. Precision is necessary, because the remaining crank travel determines how much force will be applied to the valve plug to achieve tight shutoff.
  • Page 15: Troubleshooting

    TROUBLESHOOTING 4. Verify fuse continuity. No valve movement: 5. Verify circuit board status. If status is normal, after the fail safe 1. Check that operating power and signal are present at the capacitors have fully charged and the LED goes out, the LED motor terminals.
  • Page 16: Typical Assembly Drawings

    D3400007 THIS DRAWING AND THE DEVICE, PROCESS, METHOD AND/ OR PRODUCT SHOWN THEREIN ARE THE PROPRIETARY PROPERTY OF WARREN CONTROLS INCORPORATED. THIS DRAWING IS FOR REFERENCE PURPOSES ONLY. POSSESSION OF IT DOES NOT IN ITSELF CONVEY ANY RIGHT OR LICENSE...
  • Page 17 D3400007 AmurAct AMURACT_IOM_RevK_0415...
  • Page 18 D3400011 THIS DRAWING AND THE DEVICE, PROCESS, METHOD AND/ OR PRODUCT SHOWN THEREIN ARE THE PROPRIETARY PROPERTY OF WARREN CONTROLS INCORPORATED. THIS DRAWING IS FOR REFERENCE PURPOSES ONLY. POSSESSION OF IT DOES NOT IN ITSELF CONVEY ANY RIGHT OR LICENSE...
  • Page 19 D3400011 AmurAct AMURACT_IOM_RevK_0415...
  • Page 20 D3400014 THIS DRAWING AND THE DEVICE, PROCESS, METHOD AND/ OR PRODUCT SHOWN THEREIN ARE THE PROPRIETARY PROPERTY OF WARREN CONTROLS INCORPORATED. THIS DRAWING IS FOR REFERENCE PURPOSES ONLY. POSSESSION OF IT DOES NOT IN ITSELF CONVEY ANY RIGHT OR LICENSE...
  • Page 21 D3400014 AmurAct AMURACT_IOM_RevK_0415...
  • Page 22 D3400015 THIS DRAWING AND THE DEVICE, PROCESS, METHOD AND/ OR PRODUCT SHOWN THEREIN ARE THE PROPRIETARY PROPERTY OF WARREN CONTROLS INCORPORATED. THIS DRAWING IS FOR REFERENCE PURPOSES ONLY. POSSESSION OF IT DOES NOT IN ITSELF CONVEY ANY RIGHT OR LICENSE...
  • Page 23 D3400015 AmurAct AMURACT_IOM_RevK_0415...
  • Page 24: Amuract_ Iom_Revk_0415

    AmurAct Actuator Linkage and Motor AMURACT_ IOM_RevK_0415 2600 EMRICK BLVD • BETHLEHEM, PA 18020 • USA •800-922-0085 • WWW.WARRENCONTROLS.COM DEPENDABLE, RUGGED, PRECISION CONTROL VALVES AND ACCESSORIES 92500060 Rev K...

This manual is also suitable for:

Amuract linkage le series

Table of Contents