SIL qualification. These manuals are available on our homepage. Operating instructions VEGABAR 82 - Secondary sensor for electronic differential pressure: Document-ID 45050 Editing status of the quick setup guide: 2022-04-20 VEGABAR 82 • Secondary sensor for electronic differential pressure...
During work on and with the device, the required personal protective equipment must always be worn. Appropriate use As Secondary Device, the VEGABAR 82 is part of an electronic dif- ferential pressure meaasurement. You can find detailed information about the area of application in chapter "...
The environment management system is certified according to DIN EN ISO 14001. Please help us fulfil this obligation by observing the environmental instructions in this manual: • Chapter " Packaging, transport and storage" • Chapter " Disposal" VEGABAR 82 • Secondary sensor for electronic differential pressure...
Alternatively, you can access the data via your smartphone: • Download the VEGA Tools app from the " Apple App Store" or the " Google Play Store" • Scan the QR-code on the type label of the device or •...
The following requirements must be fulfilled: • Configuration of the sensor suitable for electronic differential pres- sure • Pressure type is identical for both sensors, i.e. relative pressure/ relative pressure or absolute pressure/absolute pressure VEGABAR 82 • Secondary sensor for electronic differential pressure...
Page 7
Total pressure: 0.8 bar + 0.05 bar = 0.85 bar Instrument selection Nominal measuring range Primary: 1 bar Nominal measuring range Secondary: 1 bar Turn Down: 1 bar/0.050 bar = 20 : 1 VEGABAR 82 • Secondary sensor for electronic differential pressure...
Page 8
Secondary (static or superimposed pressure) are output by the sensor. Depending on the instrument version, output as 4 … 20 mA signal or digitally via HART, Profibus PA or Foundation Fieldbus. VEGABAR 82 • Secondary sensor for electronic differential pressure...
Fig. 3: Connection steps 5 and 6 5. Insert the wire ends into the terminals according to the wiring plan 6. Check the hold of the wires in the terminals by lightly pulling on them VEGABAR 82 • Secondary sensor for electronic differential pressure...
Connection cable Supply and signal circuit Primary Device Connect shielding here. Connect ground terminal on the outside of the hous- ing to ground as prescribed. The two terminals are galvanically connected. VEGABAR 82 • Secondary sensor for electronic differential pressure...
Page 11
The connection between Primary and Secondary Device is carried out acc. to the table: Primary Device Secondary Device Terminal 5 Terminal 5 Terminal 6 Terminal 6 Terminal 7 Terminal 7 Terminal 8 Terminal 8 VEGABAR 82 • Secondary sensor for electronic differential pressure...
In this menu item you carry out the min. adjustment for level. Enter the percentage value and the corresponding pressure value for the min. level. Max. adjustment In this menu item you carry out the max. adjustment for level. VEGABAR 82 • Secondary sensor for electronic differential pressure...
Page 13
Enter the corresponding pressure value for 0 %. Span adjustment In this menu item you carry out the Span adjustment for the differen- tial pressure Enter the corresponding pressure value for 100 %. VEGABAR 82 • Secondary sensor for electronic differential pressure...
Page 14
Enter the percentage value and the corresponding height of the interface. Max. adjustment In this menu item, you carry out the adjustment for the max. height of the interface. Enter the percentage value and the corresponding height of the interface. VEGABAR 82 • Secondary sensor for electronic differential pressure...
Page 15
The quick setup for density-compensated level measurement is hence finished. Parameterization example VEGABAR 82 always measures pressure independently of the pro- cess variable selected in the menu item " Application". To output the selected process variable correctly, an allocation of the output signal to 0 % and 100 % must be carried out (adjustment).
The main menu is divided into five sections with the following func- tions: Setup: Settings, e.g., for measurement loop name, application, units, position correction, adjustment, signal output Display: Settings, e.g., for language, measured value display, lighting VEGABAR 82 • Secondary sensor for electronic differential pressure...
Units Unit of measure- mbar (with nominal measuring range ment ≤ 400 mbar) bar (with nominal measuring ranges ≥ 1 bar) Static pressure Position correc- 0.00 bar tion VEGABAR 82 • Secondary sensor for electronic differential pressure...
Page 18
Peak value Pressure Current pressure measured value Pointer function Temperature Actual measuring cell and electronic temp. temperature Simulation Pressure, percent, signal output, linearized per- cent, measuring cell temperature, electronics tem- perature VEGABAR 82 • Secondary sensor for electronic differential pressure...
Page 19
100.00 %, 1 m Special pa- Service-Login No reset rameters Info Menu item Parameter Device name VEGABAR 82 Instrument version Hardware and software version Factory calibration date Date Sensor characteristics Order-specific characteristics VEGABAR 82 • Secondary sensor for electronic differential pressure...
Black, blue Connection cable Secondary - Primary, electrical data Ʋ Wire cross-section 0.34 mm² (AWG 22) Ʋ Wire resistance < 0.05 Ω/m (0.015 Ω/ft) IP66/IP68 (0.2 bar), only with absolute pressure. VEGABAR 82 • Secondary sensor for electronic differential pressure...
Page 21
12 V DC B min Ʋ U with lighting switched on 16 V DC B min Ʋ U Depending on the signal output and version of the B max Primary Devices VEGABAR 82 • Secondary sensor for electronic differential pressure...