PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII)
Panel
-
-
Outputs Marked * have the tone selection option
ACTIONS (MODIFY)
For each ACTION (Cause & Effect) previously selected you can:
Change Input Selection, i.e. Point / Zone / Loop / Panel etc.
Change Output Selection, i.e. Point / Zone / Loop / Panel etc.
Erase one or more previous action
Exit to New / Modify

11- DISABLEMENTS

11.1 DISABLEMENT

To aid commissioning and assist routine maintenance checks, various functions of the Quatro fire alarm system can be disabled as
described below.

11.2 ZONE DISABLEMENT

When a zone is disabled, the panel will not respond to any fault or fire signals it receives from DETECTORS from that zone.
This might be used if the system requires routine maintenance, and the user needs the rest of the system to continue running, but
doesn't want spurious false alarms.
The panel will respond in the usual manner to any events in any non-disabled zones.
Any number of zones can be disabled, but it is good practice to only disable one zone at a time.
A zone can be disabled as follows:
Turn the key switch clockwise to the Controls Enabled Position. The controls Active LED will light.
Press any key followed by the Level 1 password (default 1111).
Select Zones then Disable. Enter the zone(s) or range of zones to be disabled.
Finally select Accept and then Exit.
When zones have been disabled, the General Disablement LED will be lit and also the zonal disablement LEDs (in one or both of the
columns labelled FAULT DISABLE TEST). The zonal disablement LEDs only apply to zones 1 to 20.
When one or more zones have been disabled, the main screen on the LCD display changes from SYSTEM NORMAL to DISABLED
ZONES, as shown.
In the example, line 2 indicates that a total of 9 zones have been disabled, and
the 5th of these is shown on line 3. Zone 1 (Z001) has the text label FIRST FLOOR.
The zone no. and text label for each disabled zone can be displayed by pressing
Doc No: GLT-215-7-1
www.acornfiresecurity.com
RMT/No/Yes (1-032)
(000–999)
Issue: 1.36
Author: NJ/TE
www.acornfiresecurity.com
Firmware Versions: PANEL 1.84 & LOOP 3.70
Delay
Outputs ON
Outputs OFF
Sounders ON*
Sounders OFF
Relays ON
Relays OFF
PCB Sounder One ON
PCB Sounder One
OFF
PCB Sounder Two ON
PCB Sounder Two
OFF
DISABLED ZONES
Z001 – FIRST FLOOR
[ - ]
DATE: 25/05/2017
Alarm + Flash
Alert + Flash
Emergency + Flash
Flasher
Alarm
Alert
Emergency
18/08/15 09:38
005/009
[ + ]
47