Dimensional drawings:
MaxLED 26
Installation:
1
The product contains bracket for wall mounting and spacers for ceiling mounting.
Step 1: Fasten the mounting part (with screws from within) to either wall bracket (supplied), ceiling (with or without supplied
spacers), pendulum, wire or flag bracket. If mounted close to a wall, make sure that the unlock button is facing
outwards.
Pass the mains cables through the cable gland. Connect the mains cables to terminal blocks: L for live
wire, N for neutral and PE for ground. Tighten the cable tie around the cables
Step 2: To insert the pictograms, first unscrew the two screws holding the side profile (see picture). Remove the profile,
insert the pictograms and refit the side profile.
Step 3: Slide the luminaire into the socket.
installed. To dismantle the luminaire, push the lock/unlock button, slide the luminaire to the left and pull it down.
NOTE! The light source is non-replaceable.
At the end of their useful life the
packaging and product should be
disposed of via a suitable
recycling centre. Do not dispose
of with your normal household
waste. Do not burn.
Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway
MaxLED
Centralized
MaxLED 47
2
The lock/unlock button appears indicating that the luminaire is securely
Technical description
Part no.:
Lumen output:
Weight:
Maximum power consumption:
Operation voltage:
Ambient temperature range:
Relative humidity:
Classification:
IP40
MaxLED 65
3
.
MaxLED26
MaxLED47
290267
290266
280 lm
500 lm
970g
1450g
2.6W/2.9VA
5.1W/5.4VA
140-250V DC/AC 50-60Hz
-30 to +50°C
Up to 95%
EN 60598-2-22
GB
MaxLED65
290268
850lm
2200g
8.2W/8.6VA