Gas Burner Safety Control DKG 972
For 2-stage atmospheric gas burners
Flame detection:
- Ionisation probe
- Infrared-flicker detector IRD 1020.1
- UV flame sensor UVD 971
INTRODUCTION
The burner control box DKG 972 controls and supervises
atmospheric burners for gas. They are approved and certified
according to the applicable European standards and
regulations.
The microprocessor-based programming sequence ensu-
res extremely stable timings independent of voltage varia-
tions, ambient temperature and/or switch-on cycles. The
built-in information system not only provides a continuous
monitoring of the actual state of the box (very helpful es-
pecially for monitoring the start-up phase) but also informs
about the cause of a possible lock out. The lock out cause
is stored in such a way that it can be retrieved even after a
power failure.
The control box is designed for maximum safety in case of
fluctuations in the voltage supply. If the mains voltage drops
below the permitted level, operation is interrupted and the
control box automatically prevents the start sequence from
being repeated. In this way, the safety of the system is not
put at risk by a drop in the mains voltage. This low-voltage
protection works not only during start-up but also perma-
nently during operation.
CONSTRUCTIONAL FEATURES
The control box circuitry is protected by a flame resistant,
transparent plug-in type plastic housing. A central fixing
screw locks the control box to the wiring base.
The plug-in control box incorporates the microprocessor
based timer, flame check and reset circuits.
Manual reset from lock out and set to lock out is provided by
a push button with an integrated LED information system.
A variety of cable entry points provides complete flexibility
for electrical wiring.
The wiring base S98 is equipped with spare- and extraterminals
and allows together with a variety of cable entry points utmost
flexibility of electrical wiring.
The DKG 972 are compatible with the TFI 812.
Different are only the pre- and post-ignition times.
Max. heating power according the limits in the Gas Appliance
Directive.
Table of timings (sec.)
Model
waiting time start
tw
05
12
10
12
pre-ignition time
Stray light monitoring
tvz
3
3
TECHNICAL DATA
Operating voltage
or
Fuse rating
Power consumption
Max. load per output
- term. 3 ignition trafo
- term. 5 + 6 solenoid valves
- term. 7 alarm indicator
- term. 4 auxiliary blower
total load
Reset time from lock out
Re-cycling / repetition (max. 4x) after a loss-of-flame during
operation
Sensitivity
min. ionisation current required
Sensitivity for stray light
Ionisation probe insulation
Stray capacitance
max. cable length
Flame detectors
IRD 1020.1
UVD 971
Weight incl. Wiring base
Mounting position
Protection class
Approved ambient parameter
for control and flame detector
- for operation
- for storage
Build-up of ice, penetration of
water and condensing water are
Approvals according
to European standards
Classified acc. to EN 298
safety time
tf
ts
5
5
5
10
1
220 / 240 V (-15... +10%)
50 Hz (±5%)
110 / 120 V (-15... +10%)
60 Hz (±5%)
10 A fast, 6 A slow
ca. 12 VA
1.0 A, cos ϕ 0.2
0.5 A, cos ϕ 0.4
0.5 A, cos ϕ 0.4
2.0 A, cos ϕ 0.4
4.0 A, cos ϕ 0.4
max. 16 A during 0,5 sec
none
1 µA
1.5 µA
0.4 µA
probe - earth
greater than 50 MΩ
probe- earth
less then 1000 pF
< 3 m
side-on or end-on viewing
end-on viewing
190 g
any
IP 40
max. 95% at 30° C
-20° C... +60° C
-20° C... +80° C
inadmissible
EN 298 and EN 230, as
well as all other relevant
Directives and standards
ATLLXN
post-ignition time
delay 2nd-stage
tn
tv2
4
25
9
25