HONEYWELL EXCEL 5000 OPEN SYSTEM
GENERAL INFORMATION
Depending on your application's hardware requirements, you
can choose between the following different Excel 12 models:
W7704A1004
•
230 Vac power supply; length 180 mm
•
five relays (incl. three normally-open relays and two
changeover relays) and four triac outputs
•
four binary inputs
•
seven analog inputs
•
two analog outputs (0...10 V)
•
one LED output
W7704B1002
•
230 Vac power supply; length: 180 mm
•
three normally-open relays and six triac outputs
•
four binary inputs
•
seven analog inputs
•
two analog outputs (0...10 V)
•
one LED output
W7704C1000
•
24 Vac power supply; length: 126 mm
•
six triac outputs
•
four binary inputs
•
seven analog inputs
•
two analog outputs (0...10 V)
•
one LED output
W7704D1008
•
24 Vac power supply; length: 126 mm
•
five relays (incl. three normally-open relays and two
changeover relays) and six triac outputs
•
four binary inputs
•
seven analog inputs
•
two analog outputs (0...10 V)
•
one LED output
W7704D1016
•
230 Vac power supply; length: 180 mm
•
five relays (incl. three normally-open relays and two
changeover relays) and six triac outputs
•
four binary inputs
•
seven analog inputs
•
two analog outputs (0...10 V)
•
one LED output
® U.S. Registered Trademark
Copyright © 2005 Honeywell Inc.
All Rights Reserved
INSTALLATION INSTRUCTIONS
W7704D1024 (for Japan, only)
•
100 Vac power supply; length: 180 mm
•
five relays (incl. three normally-open relays and two
changeover relays) and six triac outputs
•
four binary inputs
•
six analog inputs, plus AI6 (which is suitable for
reading input from LESST wall modules, only)
•
two analog outputs (0...10 V)
•
one LED output
W7704E1005 (for Japan, only)
•
24 Vac power supply; length: 126 mm
•
two relays (both normally-open) and three triac outputs
•
four binary inputs
•
two analog inputs, plus AI6 (which is suitable for
reading input from LESST wall modules, only)
•
one analog output (0...10 Vdc)
W7704F1003
•
230 Vac power supply; length 180 mm
•
four relays (incl. three normally-open relays and one
changeover relay) and four triac outputs
•
four binary inputs
•
two analog inputs
•
two analog outputs (0...10 V)
•
one LED output
BEFORE INSTALLATION
IMPORTANT
It is recommended that the Excel 12 be kept at room
temperature for at least 24 hours before applying
power; this is to allow the evaporation of any
condensation resulting from low shipping / storage
temperatures.
CAUTION
To avoid electrical shock or equipment damage, you
must turn off the power supply before attaching /
removing connections to/from any terminals.
Mounting
The Excel 12 is available with either short (W x L x H =
126 x 76 x 110 mm) or long (W x L x H = 180 x 76 x 110 mm)
housings (see Fig. 1) conforming to IP20/30. The mounting
procedures are similar for both sizes.
The Excel 12 is suitable for mounting on a standard rail (DIN
EN 50022-35 x 7,5) and for installation in wiring cabinets, in
fuse boxes, and on walls/ceilings.
Excel 12
W7704
EN1B-0201GE51 R0905C