Page 2
In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
Mounting, installation and wiring are covered in other documents. Honeywell does not recommend using devices for critical control where there is a single point of failure or where single points of failure result in unsafe conditions. OneWireless is targeted at open loop control, supervisory control, and controls that do not have environmental or safety consequences.
Chassis Ground: Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements. continued OneWireless XYR 6000 Pressure Transmitter R120 User's Manual Revision 8 November 2010...
Page 7
47 of the NZ Trade Marks Act. The mark is only to be used in accordance with conditions laid down by ACMA and RSM. This mark is equal to the CE Mark used in the European Union. N314 directly under the logo is Honeywell’s unique supplier identification number. Revision 8...
Details of topics that relate uniquely to the Honeywell XYR 6000 Pressure Transmitter, This manual does not cover installation, mounting, or wiring. See XYR 6000 Transmitter Quick Start Guide (document 34-XY-25-21). OneWireless network overview OneWireless is an all digital, serial, two-way communication mesh network that interconnects industrial field sensors to a central system.
Bulgaria Lithuania Cyprus Malta Czech Republic Netherlands Denmark Norway Estonia Poland Finland Portugal France Romania Germany Slovakia Greece Slovenia Hungary Spain Iceland Sweden Ireland Switzerland Italy United Kingdom Revision 8 OneWireless XYR 6000 Pressure Transmitter R120 User's Manual November 2010...
Class II and III installations and Type 4X/IP66 applications require that all cable and unused entries be sealed with a NRTL (National Recognized Testing Laboratory) listed cable gland or conduit plug. Cable glands and conduit plugs are not supplied with the product. OneWireless XYR 6000 Pressure Transmitter R120 User's Manual Revision 8 November 2010...
Intentional or unintentional changes or modifications must not be made to the XYR 6000 Wireless Transmitters unless under the express consent of the party responsible for compliance. Any such modifications could void the user’s authority to operate the equipment and will void the manufacturer’s warranty.
European Union restriction The XYR 6000 Wireless Transmitters are in conformity with the applicable portions of the ETSI standards as required by the R&TTE Directive 1999/5/EC. France restricts outdoor use to 10mW (10dBm) EIRP in the frequency range of 2,454-2,483.5 MHz.
2. Specifications 2.4. Honeywell European (CE) Declaration of Conformity (DoC) Honeywell European (CE) Declaration of Conformity (DoC) This section contains the European Declaration of Conformity (DoC) statement, for the XYR 6000 OneWireless products. R&TTE ATEX 1999/5/EC 73/23/EEC 2004/108/EC 94/9/EC Directive...
Transmitters is in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC. Español Por medio de la presente Honeywell declara que el XYR 6000 (Spanish): Wireless Transmitters cumple con los requisitos esenciales y cualesquiera otras disposiciones aplicables o exigibles de la Directiva 1999/5/CE.
ATEX Conditions for Safe Use Because the enclosure of the enclosure of the XYR 6000 Wireless Transmitter is made from aluminum, if it mounted in an area where the use of category 1G apparatus is required, it must be installed such that even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded.
3.1. Installation 3. Preparation Installation Refer to the XYR 6000 Transmitter Quick Start Guide (document 34-XY-25-21) for installation, mounting and wiring of your XYR 6000 transmitter. Configuration The XYR 6000 Transmitter contains the electronics interface compatible for connecting to the OneWireless network.
If successful the display will briefly show “ZERO SET”. If unsuccessful the display will briefly show “ERROR”. Exit the menu. Reverse step 1. When ready, in Wireless Builder return the transmitter’s channel to service and set Write Lock to Locked. Revision 8 OneWireless XYR 6000 Pressure Transmitter R120 User's Manual November 2010...
Each of these blocks contains parameters that are standard WNSIA-transmitter defined parameters. The AITB and device blocks contain standard parameters common to all XYR 6000 transmitter models (that is, pressure, temperature, DI, corrosion, HLAI) as well as pressure-specific parameters. The radio block contains parameters for communication with the wireless network.
WFN ID by accessing the quick view mode using the Authentication Device navigation keys. For more information on parameters, refer to the following documents. OneWireless Wireless Builder User’s Guide OneWireless Parameter Reference Revision 8 OneWireless XYR 6000 Pressure Transmitter R120 User's Manual November 2010...
Device Local Configuration buttons (Table 7). Authentication Device menus are described in section 5.6 starting on page 22. OneWireless XYR 6000 Pressure Transmitter R120 User's Manual Revision 8 November 2010...
Transmitter has connected with only one order to form a redundant connection to the Multinode. network *Use the PDA to determine your radio firmware build number (page 21). Revision 8 OneWireless XYR 6000 Pressure Transmitter R120 User's Manual November 2010...
Millimeters of water at 4°C MMH2O 68F Millimeters of water at 68° F INHG 0C Inches of mercury at 0° C MMHG 0C Millimeters of mercury at 0° C PERCENT Percent OneWireless XYR 6000 Pressure Transmitter R120 User's Manual Revision 8 November 2010...
32. invalid. OVR TEMP Over Temperature The meter body has Determine cause excessive exceeded the maximum temperature. temperature as defined by the meter body characterization data. Revision 8 OneWireless XYR 6000 Pressure Transmitter R120 User's Manual November 2010...
Page 30
Restart both the radio and sensor. detected on Sensor If condition persists, replace Board. Could be caused sensor module. See page 32. by one of the status items marked by *. OneWireless XYR 6000 Pressure Transmitter R120 User's Manual Revision 8 November 2010...
Page 31
Calibrate using the lower and upper trim points. blank* Device/Firmware Sensor Board Firmware Replace sensor module. See page Mismatch* Error. The software did not pass verification tests. Revision 8 OneWireless XYR 6000 Pressure Transmitter R120 User's Manual November 2010...
SDREV Sensor device revision SBLD Sensor build number Radio Type DSSS RBLD Radio build number Wireless field network identifier Network device address MODE/CHANNEL Frequency hopping mode & channel OneWireless XYR 6000 Pressure Transmitter R120 User's Manual Revision 8 November 2010...
Secondary receive signal strength. Same as PRI RSSI. Read only. WFN ID Wireless Field Network ID. Read only. DEV ADD Device address. Read only. TX POWER Radio transmit power. Read only. Revision 8 OneWireless XYR 6000 Pressure Transmitter R120 User's Manual November 2010...
Main menu The main menu is shown below. Details start on the next page. Figure 3 Main menu OneWireless XYR 6000 Pressure Transmitter R120 User's Manual Revision 8 November 2010...
PDA, clear the transmitter’s key and reset its configuration to factory default (such as for decommissioning). Figure 4 Security and Node Deployment Revision 8 OneWireless XYR 6000 Pressure Transmitter R120 User's Manual November 2010...
Page 36
For more details on keys, refer to Getting Started with Honeywell OneWireless Solutions. OneWireless XYR 6000 Pressure Transmitter R120 User's Manual...
Go to the upper menu level. When changing a number value, move cursor to the left/more significant digit, then wrap around to the least significant digit. Revision 8 OneWireless XYR 6000 Pressure Transmitter R120 User's Manual November 2010...
Range: 0 to 65535. Build Sensor firmware and radio firmware build numbers. Radio Hardware radio type, FHSS or DSSS WFN ID: Wireless Field Network ID. Range: 0 to 255. OneWireless XYR 6000 Pressure Transmitter R120 User's Manual Revision 8 November 2010...
Page 39
If successful, the device will transition to the connected state. Connected – A secure connection is formed with one or two multinodes. The second line contains detailed state information useful for problem reporting. Revision 8 OneWireless XYR 6000 Pressure Transmitter R120 User's Manual November 2010...
Port infrared communication is not functioning, you can override the detected settings using this option. Read TX Power Level Reads the transmission power level of the transmitter radio. OneWireless XYR 6000 Pressure Transmitter R120 User's Manual Revision 8 November 2010...
Replacement of damaged parts such as the transmitter display/sensor and batteries. Preventive maintenance The XYR 6000 transmitter itself does not require any specific maintenance routine at regularly scheduled intervals. However, you should consider carrying out these typical inspection and maintenance routines on a schedule that is dictated by the characteristics of the process medium being measured and whether blow- down facilities or purge systems are being used.
Use a torque wrench to gradually tighten nuts to torque rating shown in Table 10, in sequence shown in Figure 8. Tighten head bolts in stages of 1/3 full torque, 2/3 full torque, and then full torque. Return transmitter to service. OneWireless XYR 6000 Pressure Transmitter R120 User's Manual Revision 8 November 2010...
Table 11 Sensor module replacement Step Action Honeywell recommends that the transmitter be removed from service and moved to a clean area before servicing. Loosen the M3 locking set screw on the display end-cap. See item 1 in Figure 9. Unscrew and remove the end cap.
Batteries must not be changed in an explosive gas atmosphere. If IS Battery Pack, Honeywell 50047517-001, has been installed in the Wireless Transmitter, the transmitter enclosure maybe opened when an explosive gas atmosphere is present. Otherwise, do not open transmitter enclosure when and explosive gas atmosphere is present.
0.4 to 0.6 N-M (3.5 – 5.3 Lb-in). Reconnect the Battery Pack connector Honeywell recommends lubricating the end cap with a silicone grease such as Dow Corning #55 or equivalent before replacing the end cap Screw the cap back on and tighten the M3 locking screw...
Disconnect all power from transmitter input sources before accessing the 24V power module. Failure to do so could result in death or serious injury if the input terminals or wires are accidentally touched. OneWireless XYR 6000 Pressure Transmitter R120 User's Manual Revision 8 November 2010...
0,4 – 0,6 N-M (3.5 – 5.3 Lb-in). Re-connect battery connector. Honeywell recommends lubricating the end cap O-ring with a Silicone Grease such as Dow Corning #55 or equivalent before replacing the end cap. Screw the end cap back on and tighten the M3 locking screw.
POTENTIAL ELECTROSTATIC CHARGING HAZARD The integrally mounted antenna shroud is made of Teflon® and has a surface resistance greater than 1G ohm per square. When the XYR 6000 transmitter is installed in potentially hazardous locations care should be taken not to electrostatically charge the surface of the antenna shroud by rubbing the surface with a cloth, or cleaning the surface with a solvent.
See items 2 in Figure 12. Torque screws to 0,4 – 0,6 N-M (3.5 – 5.3 Lb- in). Replace the front end cap. Honeywell recommends lubricating the front end cap O-ring with a Silicone Grease such as Dow Corning #55 or equivalent before replacing the end cap.
6. Maintenance/Repair 6.8. Parts Parts Transmitter body The following replacement parts may be ordered from Honeywell. Part number Qty. Description 50015866-502 ELECTRONICS MODULE ASSEMBLY aka SENSOR MODULE for Pressure 50015866-506 ELECTRONICS MODULE ASSEMBLY aka SENSOR MODULE for Pressure- Intrinsically Safe...
6. Maintenance/Repair 6.8. Parts Meter body Use the following figures and table to find replacement parts. Figure 13 STDW924, STDW930, STDW974 Figure 14 STGW944, STGW974 Revision 8 OneWireless XYR 6000 Pressure Transmitter R120 User's Manual November 2010...
NOTE 2: The Kit for Process Heads without side vent/drain does not include Pipe Plugs (K1). Reference Head: 51452951-001 Carbon Steel Blind Reference Head 51452951-002 316 SS Blind Reference Head (Model Selection Guide HR Option) OneWireless XYR 6000 Pressure Transmitter R120 User's Manual Revision 8 November 2010...
Meter body nameplate 30757503-001 Electronics enclosure seals kit for LGP/LAP models. Kit includes: ……..…….…………… O-ring for transmitter end caps ………………………… O-ring, meter body to electronics housing Revision 8 OneWireless XYR 6000 Pressure Transmitter R120 User's Manual November 2010...
Dimension drawings Dimension drawings are available for each transmitter model. If you need a copy of a drawing, please determine the appropriate drawing number from the following tables and contact your Honeywell representative. Table 17 Drawing numbers for DP models STDW924, STDW930, STDW974 Angle Bracket (“MB”...
Page 62
Phone: +(662) 693-3099 China – PRC - Chengdu FAX: +(662) 693-3089 Brazil Honeywell China Inc. Italy MIDDLE EAST Honeywell do Brasil & Cia Honeywell S.p.A. Phone: +(86-28) 8678- Taiwan R.O.C. Abu Dhabi U A E Phone: +(55-11) 7266-1900 Phone:+390292146307 6348 Honeywell Taiwan Ltd.