Section 12
12.1
12.2
RER620
Technical Manual
Relay physical connections
All external circuits are connected to the terminals on the rear panel of the relay.
Connect each signal connector (X100 and X110) terminal with one 14 or 16 Gauge
wire. Use 12 or 14 Gauge wire for CB trip circuit.
Connect each ring-lug terminal for signal connector X120 with one of maximum 14
or 16 Gauge wire.
Connect each ring-lug terminal for CTs/VTs with one 12 Gauge wire.
Protective ground connections
Figure 313:
The protective ground screw is located between connectors X100 and
X105
The ground lead must be at least 4.0 mm
Communication connections
The front communication connection is an RJ-45 type connector used mainly for
configuration and setting.
Depending on order code, several rear port communication connections are available.
Section 12
Relay physical connections
2
and as short as possible.